background image

20

Instruction Book    

IB019008EN   October 2016   www.eaton.com

FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

6.3.5 Inspection After Short Circuit

The magnitude of a short circuit may exceed the damage threshold 

of the vacuum bottle on the V201 contactor.  After a short circuit, 

the unit should be examined for any apparent physical damage, 

or deformation of the conductor bars.  If there is any evidence of 

severe stress, it is recommended that the unit be replaced.  If the 

over-travel has changed significantly (from the last inspection) on one 

or more bottles, the unit should be replaced.
A dielectric test may be performed at 1760 Vac (80% of factory test 

level) (see Section 6.6).  A dielectric test would not by itself confirm 

that the unit should be returned to service after a fault.  Vacuum 

Integrity is to be performed at 5.5 kVac RMS per Section 6.4.  

However, if there is no physical evidence of stress, and if the over-

travel exceeds the 0.020 in. (0.51 mm) minimum, the bottles can 

then be dielectrically tested as outlined in this manual.  If physical 

stress, over-travel, and dielectric are satisfactory, it is reasonable 

to return the unit to service after a fault and after unit has been 

properly cleaned.

6.4 Vacuum Interrupter Integrity Test

Vacuum interrupters used in the LV-VSR are highly reliable 

interrupting contactors.  Satisfactory performance of these devices 

is dependent upon the integrity of the vacuum in the interrupter and 

the internal dielectric strength.  Both of these parameters can be 

readily checked by a one minute AC high potential test.  During this 

test, the following warning must be observed.

WARNING

APPLYING ABNORMALLY HIGH VOLTAGE ACROSS A PAIR OF CONTACTS 

IN VACUUM MAY PRODUCE X-RADIATION.  THE RADIATION MAY 

INCREASE WITH THE INCREASE IN VOLTAGE AND/OR DECREASE IN 

CONTACT SPACING.  X-RADIATION PRODUCED DURING THIS TEST 

WITH RECOMMENDED VOLTAGE AND NORMAL CONTACT SPACING IS 

EXTREMELY LOW AND WELL BELOW THE MAXIMUM PERMITTED BY 

STANDARDS.  HOWEVER, AS A PRECAUTIONARY MEASURE AGAINST THE 

POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE 

AND/OR BELOW NORMAL CONTACT SPACING, IT IS RECOMMENDED THAT 

ALL OPERATING PERSONNEL STAND AT LEAST 3.2 FEET (1 METER) AWAY 

IN FRONT OF THE LV-VSR.

Only use an AC high potential test set.  A DC high potential test may 

result in inaccurate test results.

1.  Conduct the test with the LV-VSR open and securely placed on a 

workbench or suitable surface.

2.  Short the CTs and the secondary block connections to ground.
3.  Connect all top primary studs (bars) together and the high 

potential machine lead.

4.  Connect all bottom studs together.  Do not ground them to the 

LV-VSR frame.  Connect the high potential ground to the bottom 

studs.

5.  Start the machine at zero potential, then increase to 5.5 kV AC 

RMS and maintain for one minute.

6.  Successful withstand indicates that all interrupters have 

satisfactory vacuum levels.  If there is a breakdown, the contactor 

should be replaced before placing the LV-VSR in service.

7.  After the high potential is removed, discharge any electrical 

charge that may be retained, particularly from the center shield 

of vacuum interrupters.  To avoid any ambiguity in the AC high 

potential test due to leakage or displacement (capacitive) current, 

the test unit should have sufficient volt-ampere capacity.  It is  

recommended that the equipment be capable of delivering  

25 milliamperes for one minute.

8.  Remove ALL shorting wire on CTs and secondary block before 

placing unit back into service.

WARNING

FAILURE TO REMOVE ALL SHORTING WIRE FROM THE CURRENT 

TRANSFORMERS AND SECONDARY CONNECTIONS MAY CAUSE INJURIES 

AND EQUIPMENT DAMAGE. 

 

DC HIGH POTENTIAL TESTS ARE NOT RECOMMENDED ON VACUUM 

INTERRUPTER ASSEMBLIES.

6.5 Insulation

In LV-VSRs, insulation maintenance primarily consists of keeping 

all insulating surfaces clean.  This can be done by wiping off all 

insulating surfaces with a dry lint free cloth.  In case there is any 

tightly adhering dirt that will not come off by wiping, it can be 

removed with a mild solvent or distilled water.  Be sure that the 

surfaces are dry before placing the LV-VSR in service.  If a solvent is 

required to cut dirt, use isopropyl alcohol.  Secondary control wiring 

requires inspection for tightness of all connections and damage to 

insulation.

6.6 Insulation Integrity Check

Primary Circuit

The integrity of primary insulation may be checked by the AC high 

potential test.  The test voltage is 1760 V RMS, 60 Hz.  Conduct the 

test as follows.

1.  Conduct the test with the LV-VSR open and securely placed on a 

workbench or suitable surface.

2.  Ground the LV-VSR frame.
3.  Short the CTs connections to ground. 
4.  Close the contactor on the LV-VSR.  Control power will be 

needed to close the Contactor.

5.  Connect the high potential lead of the test machine to one of the 

phases of the LV-VSR. 

6.  Connect the remaining two phases and LV-VSR frame to ground. 
7.  Start the test machine with the output potential at zero and 

increase to the test voltage.  Maintain the test voltage for one 

minute. 

8.  Repeat for the remaining phases.  Successful withstand indicates 

satisfactory insulation strength of the primary circuit. 

9.  Disconnect the control power from the LV-VSR.
10. After the control power has been removed and disconnected 

from the LV-VSR, short all of the secondary connections together 

and to the frame.

11. Connect the high potential lead of the test machine to one of the 

poles of the LV-VSR. 

12. Connect the remaining poles and LV-VSR frame to ground.
13. Start the test machine with the output potential at zero and 

increase to the test voltage.  Maintain the test voltage for one 

minute. 

14. Repeat for the remaining poles.  Successful withstand indicates 

satisfactory insulation strength of the primary circuit. 

15. Remove ALL shorting wire on the CTs and secondary block 

before placing unit back in to service. 

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: