Instruction Book    

IB019008EN   October 2016   www.eaton.com

FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

Section 6: Inspection and Maintenance

6.1 Introduction

WARNING

• 

DO NOT WORK ON A LV-VSR IN THE “CONNECTED” POSITION.

• 

DO NOT WORK ON A LV-VSR WITH SECONDARY DISCONNECTS 

ENGAGED.

• 

DO NOT WORK ON A LV-VSR WITH THE CONTACTOR CLOSED, UNLESS 

IT IS REMOVED FROM THE SWITCHGEAR.

• 

DO NOT DEFEAT ANY SAFETY INTERLOCKS.

• 

FOLLOW ALL PRECAUTIONARY MEASURES WHEN TESTING FOR 

VACUUM INTEGRITY.

• 

FAILURE TO FOLLOW ANY OF THESE INSTRUCTIONS MAY CAUSE 

DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.  SEE 

SECTION 2 - SAFE PRACTICES FOR MORE INFORMATION.

6.2 Frequency of Inspection

Inspect the LV-VSR once a year when operating in a clean, non-

corrosive environment.  For a dusty and/or corrosive environment, 

inspection should be performed twice a year.  Additionally, it is 

recommended to inspect the LV-VSR every time it interrupts fault 

current.
The no-load life test value of the LV-VSR is hundreds of thousands 

of operations.  This value will be reduced if proper inspection, 

maintenance, and cleaning are not performed.
Refer to Section 6.3 for maintenance and inspection check points.

6.3 Inspection and Maintenance Procedures

It is recommended that inspection and maintenance procedures are 

performed outside of the cell.

CAUTION

SOME COMMERCIAL CLEANING AGENTS WILL DAMAGE THE 

NAMEPLATES OR MOLDED PARTS.  MAKE SURE THAT CLEANING AGENTS 

OR SOLVENTS USED ARE SUITABLE FOR THE JOB.

6.3.1 V201 Contactor

NOTICE

THERE ARE NO FIELD SERVICEABLE PARTS ON CONTACTORS.

WARNING

THE ONLY WAY TO CLOSE THE CONTACTOR IS TO ENERGIZE THE COIL.  

IF THE COIL IS ENERGIZED FOR THIS OR OTHER MAINTENANCE, USE 

ADEQUATE CARE TO GUARD AGAINST ELECTRICAL SHOCK.  DO NOT 

PERFORM ANY MAINTENANCE WITH THE LV-VSR IN THE SWITCHGEAR.

6.3.2 Contact Wear Allowance

Contact material vaporizes from the contact faces during every 

interruption and condenses inside the bottle.  This is normal and is 

provided for by over-travel or wear allowance.  When the contactor 

is fully closed, there is a gap between the pivot plate and the bottle 

nuts.  As the contacts wear, this gap decreases.  When any gap 

goes below 0.020 in. (0.51 mm), the unit should be replaced.  Use 

the 0.020 in. 0.51 mm) thick fork shaped over-travel gauge (Part 

Number 7874A59H01) supplied for this measurement.

WARNING

DO NOT READJUST THE BOTTLE NUTS TO RESET OVER-TRAVEL AS THE 

BOTTLES WEAR.  ONCE PLACED INTO SERVICE, OVER-TRAVEL SHOULD BE 

CHECKED BUT NOT ADJUSTED.

6.3.3 Mechanical Checks

WARNING

THE MECHANICAL CHECKS MAY ONLY BE PERFORMED OUTSIDE THE 

SWITCHGEAR CELL.

Use a test cabinet to operate the LV-VSR.  Operate the appropriate 

push buttons to CLOSE and OPEN the contactor.  While the 

contactor is closed, observe the over-travel gap between the pivot 

plates on the crossbar and the bottle nut on each pole.  This over-

travel gap should be no less than 0.045 in. (1.14 mm) when the 

contactor is new.  If less, refer to the Contact Wear Allowance 

section of this manual.
While the contactor is open, attempt to pull the armature forward. 

The armature should not move because it should already be firmly 

against the plastic main frame.  If it does move, refer to the Kickout 

Spring Adjustment section in this manual.

6.3.4 Kickout Spring Adjustment

The kickout spring is not disturbed by any maintenance described 

in this manual and, therefore, should not need any adjustment.  

However, when the contactor is in the OPEN position, the crossbar 

should be solidly against the frame, so that it cannot move 

any further open even when pulled.  If kickout spring is out of 

adjustment, call your closest Eaton representative.

Figure 6.1. Over-Travel Gauge

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: