FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

SECTION 4: DESCRIPTION AND OPERATION

Vacuum Contactor

Class V201 NEMA vacuum contactors are designed for the control 

of inductive or non-inductive loads at voltages between 200 and 600 

Vac.  The vacuum contactor in the LV-VSR is protected against short 

circuits above its capability by current limiting fuses.

General

The V201 contactor has its main contacts sealed inside ceramic 

tubes from which all air has been evacuated (i.e.: the contacts are 

in vacuum).  No arc boxes are required, because any arc formed 

between opening contacts in a vacuum has no ionized air to sustain 

it.  The arc simply stops when the current goes through zero as it 

alternates at line frequency.  The arc usually does not survive beyond 

the first half cycle after the contacts begin to separate.  The ceramic 

tube with the moving and stationary contacts enclosed is called a 

vacuum interrupter or a “bottle”.  A three-pole contactor has three 

vacuum bottles.  A metal bellows (like a small, circular accordion) 

allows the moving contact to be closed and pulled open from the 

outside without letting air into the vacuum chamber of the bottle.  

Both the bellows and the metal-to-ceramic seals of modern bottles 

have been improved to the point that loss of vacuum is no longer 

cause for undue concern.

Figure 4.1. V201 Non-Reversing Contactor. 

The moving contacts are driven by a molded plastic crossbar 

supported by two pre-lubricated ball bearings that are clamped in 

alignment for long life and free motion.
The contacts in an unmounted bottle (vacuum interrupter) are 

“normally-closed”, because the outside air pressure pushes against 

the flexible bellows.  For contactor duty, the contacts must be 

“normally-open” when the operating magnet is not energized.  

Therefore, the contacts of the vacuum bottles must be held apart 

mechanically against the air pressure when used in a contactor.  In 

the contactor, all of the bottles are held open by a single kickout 

spring in the rear of the contactor.  The kickout spring pulls against 

the moving armature and crossbar and thereby forces the bottles 

into the OPEN position.  In the OPEN position, the crossbar is 

pulling the moving contacts to hold them open.

Contact Force and Altitude

A vacuum contactor is affected by atmospheric pressure on the 

bellows of the vacuum bottles.  Up to an altitude of 3,300 ft (1005.8 

m), the contactor is designed to tolerate normal variations in 

barometric pressure. If the contactor is to be operated over 3,300 ft 

(1005.8 m) above sea level, consult the factory.

Contact Wear Allowance

Contact material vaporizes from the contact faces during every 

interruption and condenses inside the bottle. This is normal and is 

provided for by over-travel, or wear allowance. When the contactor 

is fully closed, there is a gap underneath the lower bottle nut and 

the pivot plate (see section 6.3.2 – Contact Wear Allowance). As 

the contacts wear, this gap decreases. When any gap goes below 

.020 in., the unit should be replaced. Use the fork-shaped over-travel 

gauge (Part No.7874A59H01) supplied for this measurement.

WARNING

DO NOT RE-ADJUST THE BOTTLE NUTS TO RESET OVER-TRAVEL.  ONCE 

PLACED INTO SERVICE, OVER-TRAVEL SHOULD BE CHECKED BUT NOT 

ADJUSTED.  A STAR-WHEEL LOCK IS INCLUDED FOR LOCKING THE BOTTLE 

NUTS OF EACH BOTTLE TO PREVENT TAMPERING.

Coil

The operating coil has a “figure eight” shape and is really two 

coils in series, with a connection at their common point. Both coils 

are encapsulated in one environment-immune coil shell, which 

also contains a full-wave bridge rectifier. When AC is connected 

directly to terminals A and B on the coil shell, the magnet excitation 

is unfiltered DC. The magnet will not chatter as AC magnets 

sometimes do, but at less than rated voltage it may hum slightly. 

A normally-closed Type L63 auxiliary contact, set to open slightly 

before the armature fully closes, is connected to terminals C and 

D on the coil shell. When adjusted correctly, this contact allows 

a relatively high current through the pickup winding, and as the 

contactor closes, the contact inserts the holding winding, which 

reduces the coil current to a low value sufficient to hold the magnet 

closed without overheating. No external resistors are required.

Overload Relay

The overload relay provides longtime overload protection and 

single phase protection. The solid-state overload relay provides 

high accuracy and enhanced protection through the use of micro-

electronic packaging technology. The overload relay comes standard 

with trip class 10, 15, and 20 trip characteristics.

Current Limiting Fuses

The current limiting fuses, class J AJT600EIB, are primarily used 

to provide short circuit protection to the vacuum contactor. During 

high-power testing, the V201 vacuum contactor was confirmed to 

properly coordinate with Ferraz Shawmut type class J AJT600EIB 

current limiting fuses. The contactor successfully withstood the let-

though energy of each fuse for a 200 kA available symmetrical fault 

at 600 Vac.

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: