Instruction Book    

IB019008EN   October 2016   www.eaton.com

FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

SECTION 1: INTRODUCTION

The purpose of this instruction book is to provide instructions for 

receiving, handling, storage, installation, operation, and maintenance 

of Type LV-VSR, Low Voltage- Vacuum Starter Replacement Units. 

These units are horizontal, draw-out type removable Vacuum Starter 

Replacements for existing LV Metal-Enclosed Switchgear with  

breakers of the same type and rating. LV-VSRs provide reliable  

control, protection, and performance, with ease of handling and 

maintenance.
This booklet is intended to be used in conjunction with the technical 

information provided with the original equipment order that includes 

but is not limited to electrical control schematics and wiring  

diagrams, installation plans, and procedures for installation and  

maintenance of accessory items.
Satisfactory performance is dependant upon proper application,  

correct installation, and adequate maintenance. It is strongly  

recommended that this instruction book be carefully read and  

followed in order to realize optimum performance and long useful life 

of the LV-VSR.
The LV-VSR consists of the following components: Current Limiting 

Fuses, Overload Relay, and V201 Vacuum Contactor.

• 

The current limiting fuses, class J (sized as required), are primarily 

used to provide short circuit protection to the vacuum contactor. 

During High-Power testing, the V201 vacuum contactor was 

confirmed to properly coordinate with Mersen class J AJT600EIB 

current limiting fuses. The contactor successfully withstood the 

let-though energy of each fuse for a 200 kA available symmetrical 

fault at 600 Vac. Other UL Class J fuses can be specified by the 

end user, as required, for proper coordination. Their let-through 

current, however, must be less than the short circuit current 

rating (SCCR) of the V201 contactor.

• 

The overload relay provides longtime overload protection and 

single-phase protection. The solid-state Overload Relay provides 

high accuracy and enhanced protection through the use of micro-

electronic packaging technology. The Overload Relay comes  

standard with Trip Class 10 and 20 trip characteristics and Manual 

or Manual/Automatic Reset. An electro-mechanical overload relay, 

Eaton type C306 may be substituted for the electronic overload 

relay. This relay is equipped with Class 20 overload relay heaters 

sized according to the motor full load current (FLC) and service 

factor. This relay has settings to select a trip threshold closest to 

the motor FLC; manual and automatic reset modes are selectable.

• 

The V201 Vacuum Contactor is designed for the control of  

inductive or non-inductive loads at voltages between 200 and 600, 

AC.

The fuses have a micro-switch mounted to the body of the fuse that 

provides blown/open indication. This switch opens the contactor and 

prevents a close operation in the event of a blown/open fuse. This 

feature also provides single-phase protection to the motor.

WARNING

MERSEN TYPE AOS-S MICROSWITCHES AND CURRENT LIMITING TYPE 

AJT FUSES SIZED AS REQUIRED BY THE APPLICANTION MUST BE USED 

TO RETAIN THE IEEE CERTIFICATION. SELECTED FUSE MUST HAVE A LET-

THROUGH LESS THAN SCCR OF CONTACTOR.

1.1 Available FP-25-LV-VSR Motor Starter Replacement

Refer to Table 1.

WARNING

SATISFACTORY PERFORMANCE OF THESE VACUUM MOTOR STARTER 

REPLACEMENT UNITS IS CONTINGENT UPON PROPER APPLICATION, 

CORRECT INSTALLATION, AND ADEQUATE MAINTENANCE. THIS 

INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN 

ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL LIFE OF 

THE VACUUM MOTOR STARTER. 

 

TYPE LV-VSR VACUUM MOTOR STARTER REPLACEMENT UNITS ARE 

PROTECTIVE DEVICES, AS SUCH, THEY ARE MAXIMUM RATED DEVICES. 

THEREFORE, THEY SHOULD NOT UNDER ANY CIRCUMSTANCE BE APPLIED 

OUTSIDE THEIR NAMEPLATE RATINGS 

 

ALL POSSIBLE CONTINGENCIES THAT MIGHT ARISE DURING 

INSTALLATION, OPERATION, OR MAINTENANCE, AND ALL DETAILS 

AND VARIATIONS OF THIS EQUIPMENT, ARE NOT COVERED BY THESE 

INSTRUCTIONS. IF FURTHER INFORMATION IS DESIRED BY THE 

PURCHASER REGARDING A PARTICULAR INSTALLATION, OPERATION, OR 

MAINTENANCE OF THIS EQUIPMENT, THE LOCAL EATON’S ELECTRICAL 

SERVICES & SYSTEMS REPRESENTATIVE SHOULD BE CONTACTED.

Table 1.  FP-25-LV-VSR

 Vacuum Motor Starter Replacement Unit Availability and Interchangeability.

Vacuum Starter Replacement Type

Rated Max. Volts 

(VAC)

Rated Continuous Current At 

60Hz (Amps)

Rated Short Circuit kA RMS 

At Rated Max. Voltage

Rated Withstand ANSI Test 

Voltage Low Freq. V RMS

FP-25-LV-VSR-425A

600

425

200

2200

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: