Instruction Book    

IB019008EN   October 2016   www.eaton.com

FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

5.3 ELECTRONIC OVERLOAD RELAY C440

The preferred overload relay provided on Eaton LV-VSR devices is the 

electronic C440 relay. The relay offers four selections of trip classes:

1.    The C440 overload device normally specified for the LV VSR 

devices is the relay that provides two trip class selections, 

10 or 20, plus a switchable ground fault trip system. The 

ground fault trip threshold is 50% of the full load ampere 

setting. See Figures 5.9 and 5.10.

Figure 5.9. C440 Overload Relay Faceplate and Functions

Figure 5.10. Ground Fault Unit

C440 NEMA Electronic Overload

1

LED (Unit Status)

3

Phase Imbalance Selection

2

FLA Dial

4

Operating Modes (Trip/Reset/Test)

LED

UNIT STATUS

1 flash / 2 seconds

Motor is running. Current < 1.15 Times the Dial Setting.

2 flash / 2 seconds

Motor is running. Current > 1.15 Times the Dial Setting.

No Flash

If the orange trip flag is visible, a trip has occurred.

No Flash

If the orange trip flag is not visible, motor is off or drawing < min FLA.

1

3

4

2

Figure 5.11. C440 Trip Current Adjustment and DIP Switches

Overload Tripping Current = 115%

Rotate FLA dial to current listed on motor nameplate for all motor 

Service Factors.

Figure 5.12. Motor Service Factor Information for the C440 

Overload Relay

2.    A second rarely used C440 overload relay is available in 

a 3-phase and single phase form. The 3-phase and single 

phase configured device allows four trip class selections: 

10, 20, 30, and 10A. Figure 5.11 shows the C440 with four 

trip class selections.

3.    Refer to Figure 5.10 or 5.11. C440 relay features include a 

push/pull button for trip and test, a push button for reset, 

and the full load current dial. Adjacent to the FLA dial, the 

C440 electronic overload relay has ‘dip’ switch selections for 

trip classes 10 or 20. (Most applications conforming to ANSI 

guidelines use trip class 20.) The second position enables 

or disables the built-in ground fault trip system. The third 

position of the ‘dip’ switch enables or disables the phase 

unbalance protection of the device. The fourth position of 

the ‘dip’ switch enables or disables automatic reset of the 

relay (see special warning about using automatic reset 

feature). An indicating light on the face of the relay signals 

when current is passing through the LV-VSR and when a 

trip has occurred. Rapid blinking of the indicating light on 

the C440 indicates that trip is imminent.  Make the preferred 

‘dip’ switch selections prior to energizing the LV VSR for the 

first time.

4.    A Full Load Current (FLA) dial is provided for selecting the 

full load current setting, calculated based on the current 

transformer ratio of the current transformers installed on 

the LV VSR and the full load current determined from the 

motor nameplate. When the C440 is set correctly, the relay 

will provide tripping at 115% of the motor full load rating in 

less than 10 seconds in accordance with UL 508. The C440 

provided has markings 1 through 5 corresponding to the 

5 ampere secondary current of the current transformers. 

These markings designate trip thresholds that correspond 

to the current passing through the windows of the current 

transformers mounted on the rear of the LV VSR. Selections 

are possible over the full range of the dial. The trip setting 

must be made according to item 6 below prior to energizing 

the LV VSR for the first time.

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: