Instruction Book    

IB019008EN   October 2016   www.eaton.com

FP-25-LV-VSR

Breaker-To-Motor Starter Conversion

5.    An electrically separate normally open (NO) contact and 

an electrically separate normally closed (NC) contact are 

provided. See Figure 5.14 for operating modes. The C440 

may be optionally equipped with various communication 

modules to allow remote functionality over Modbus, Device 

Net, Profibus, and Eithernet IP communication protocols. 

6.    Eaton LV VSRs are equipped with 300:5 or 600:5 current 

transformers as required by the continuous current 

rating shown on the nameplate of the device. The current 

transformer ratio and motor full load current must be 

known to determine the proper FLA dial setting on the 

C440 relay. That setting may be calculated by the following 

formula:

     

Set Value = Equivalent FLA x  (1/(CT Ratio) 

     

Example:    CT ratio is 300:5 300/5 = 60

Motor FLC is 120 amperes
Set Value = 120 x  (1/60) = 2.0

The C440 FLA setting may also be determined from Table 6.

otee:

N

The overload relay allows trip settings that exceed the 425 ampere 

continuous current rating of the LV VSR. Therefore, dial settings above 3.5 

are not allowed.  

7.    Figures 5.10 and 5.11 are provided for setting assistance. 

For the C440, the overload relay settings are the same 

regardless of motor service factor. 

otee:

N

The LV VSR is shipped from the Power Breaker Center with its over-

load relay set at the very lowest setting; the C440 must be properly set 

before closing the device onto a motor load.

8.    Figure 5.13 provides hot motor time-current information for 

the C440.

Figure 5.13. Average Hot Trip Curve for Three Phase Motors

Figure 5.14. Operating Modes for C440

9.    Eaton Instructional Leaflet IL04210001E provides additional 

information on the C440 overload relay.

10.   If the C440 overload relay trips after a motor overload 

condition, access the relay through the removable front 

clear polycarbonate cover, and press the reset button. The 

device should only be reset after the condition causing the 

motor overload is removed.

Table 6.  C440 Overload Relay Dial Settings

Overload Relay Dial Settings FLA with 300:5 CT

FLA with 600:5 CT

1.00

60

120

1.25

75

150

1.50

90

180

1.75

105

210

2.00

120

240

2.25

135

270

2.50

150

300

2.75

165

330

3.00

180

360

3.25

195

390

3.50

210

420

3.75

225

Exceeds VSR Current Rating

4.00

240

Exceeds VSR Current Rating

4.25

255

Exceeds VSR Current Rating

Phase Imbalance Selection for C440

When a three phase load is powered with a poor quality line, the 

voltage per phase may be unbalanced.
The effect of this if not protected results in unbalanced voltage 

which causes large unbalanced currents. It can also lead to motor 

stator windings being overloaded, causing excessive heating, 

reduced motor efficiency and reduced insulation life.
If the OL relay is switched to the “ON” position, it will take the 

starter offline if a phase drops below 50% of the other two phases.

5.4 INSERTION PROCEDURE

 DANGER

ARC-FLASH INCIDENCES WITH LV SWITCHGEAR CAN OCCUR DURING 

THE PROCESS OF INSERTING AND REMOVING LV-VSR DEVICES IN 

SWITCHGEAR CUBICLES. IT IS STRONGLY RECOMMENDED THAT PROPER 

PPE (PERSONAL PROTECTIVE EQUIPMENT) BE WORN BY PERSONNEL 

WHO INSERT/REMOVE LV-VSRS.

Содержание FP-25-LV-VSR

Страница 1: ...October 2016 Instruction Book IB019008EN FP 25 LV VSR Breaker To Motor Starter Conversion Effective FP 25 LV VSR 425A Shown...

Страница 2: ...quipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contac...

Страница 3: ...PECTION 13 5 1 CELL MODIFICATION INSTRUCTIONS 13 5 2 EXAMINATION FOR DAMAGE 14 5 3 ELECTRONIC OVERLOAD RELAY C440 15 5 4 INSERTION PROCEDURE 16 5 5 REMOVAL PROCEDURE 18 5 6 MANUAL OPERATIONAL CHECK 18...

Страница 4: ...ss 10 and 20 trip characteristics and Manual or Manual Automatic Reset An electro mechanical overload relay Eaton type C306 may be substituted for the electronic overload relay This relay is equipped...

Страница 5: ...n com FP 25 LV VSR Breaker To Motor Starter Conversion Table 2 FP 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H FP 25 LV VSR 425A 5 55 4 00 8...

Страница 6: ...R from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the se...

Страница 7: ...for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness...

Страница 8: ...sion 2 1 5 9 10 8 3 7 4 6 Figure 3 2 Front External View of FP 25 LV VSR Front External View 1 Trip Button 5 Crank Access Shutter 9 Guide Roller 2 Overload Relay Access 6 Lock Out Lock Tag 10 Racking...

Страница 9: ...P 25 LV VSR Breaker To Motor Starter Conversion Figure 3 3 Rear External View of FP 25 LV VSR Front External View 1 Secondary Contacts 3 Primary Disconnects 5 Lifting Point 2 Overload Relay Current Tr...

Страница 10: ...1005 8 m the contactor is designed to tolerate normal variations in barometric pressure If the contactor is to be operated over 3 300 ft 1005 8 m above sea level consult the factory Contact Wear Allo...

Страница 11: ...he LV VSR is being levered between the TEST and CONNECT positions Consequently it prevents the LV VSR from closing automatically even though the control close contact may have been made while the LV V...

Страница 12: ...self aligning See Insertion Procedure line contact slip type connectors The multiple finger arrangement on the LV VSR makes contact with a stationary mounted element The contact surfaces on the stati...

Страница 13: ...T INTERCHANGEABLE WITH CIRCUIT BREAKER EY ARE SUPPLIED WITH CELL CODE REJECTION PLATES DO NOT ATTEMPT TO MODIFY OR REMOVE THE NEW CELL CODE REJECTION PLATES MODIFICATIONS OR OMISSIONS OF THE CELL CODE...

Страница 14: ...and open normally 17 Perform an AC hipot test per section 6 prior to insertion into the switchgear 18 Check the V201 contactor per section 6 3 2 of this manual prior to insertion Figure 5 6 Rejection...

Страница 15: ...5 10 or 5 11 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay has dip...

Страница 16: ...re 5 13 provides hot motor time current information for the C440 Figure 5 13 Average Hot Trip Curve for Three Phase Motors Figure 5 14 Operating Modes for C440 9 Eaton Instructional Leaflet IL04210001...

Страница 17: ...r and insert the crank turn the crank clockwise until the position indicator on the starter shows CONNECT position Figure 5 18 9 Remove the racking crank the shutter will automatically be returned The...

Страница 18: ...ECTRICAL OPERATIONAL CHECKS WARNING DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE LV VSR IN THE CONNECT POSITION BECAUSE OF THE POSSIBILITY OF CONNECTING DE ENERGIZED LOAD CIRCUITS TO THE ELECTR...

Страница 19: ...O NOT PERFORM ANY MAINTENANCE WITH THE LV VSR IN THE SWITCHGEAR 6 3 2 Contact Wear Allowance Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle...

Страница 20: ...ul withstand indicates that all interrupters have satisfactory vacuum levels If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is...

Страница 21: ...is essential for maintaining the reliable performance of the mechanism The LV VSR should be re lubricated once a year The locations shown in Figure 30 should be lubricated with a drop of non syntheti...

Страница 22: ...r of the auxiliary contact plungers should bottom solidly in the closed contactor position as discussed under Magnet Operating Range If required the auxiliaries can be adjusted by resetting their moun...

Страница 23: ...general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Страница 24: ...evard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB019008EN October 2016 Eaton is a registered trademark All trademarks are property of the...

Отзывы: