5.1
Waveform Recorder
• Waveform records can be downloaded (read out) by means of the parameter setting
and evaluation software PowerPort-E.
• The waveform records can be viewed and analyzed within QualityManager (will be
installed with PowerPort-E).
• Waveform records can be converted into the COMTRADE file format by means of
QualityManager.
The waveform recorder works with 32 samples per cycle. It can be started by any of eight
configurable start signals.
The waveform record contains the measuring values including the pre-trigger time. By
means of PowerPort-E / QualityManager, the oscillographic curves of the analog (current,
voltage) and digital channels/traces can be shown and evaluated in a graphical form.
The waveform recorder has a storage capacity of 120 s (duration). The amount of records
depends on the size of each record.
Read Out Waveform Records
Within the [Operation / Recorders / Waveform rec] menu, the user can see the
accumulated waveform records.
NOTICE!
Within the [Operation / Recorders / Man. Trigger] menu, the user can trigger the
waveform recorder manually.
Deleting Waveform Records at the Panel
Within the [Operation / Recorders / Waveform rec] menu, the user can:
• Delete waveform records;
• Choose the waveform record that is to be deleted
via »SOFTKEY« »up« and »SOFTKEY« »down«;
• Call up the detailed view of the waveform record via »SOFTKEY« »right«;
• Confirm by pressing »SOFTKEY« »delete«;
• Enter the password followed by pressing the »OK« key;
• Choose whether only the current or all waveform records should be deleted; and
• Confirm by pressing »SOFTKEY« »OK«.
Configuring the Waveform Recorder
The waveform recorder can be configured in the [Device Para / Recorders / Waveform rec]
menu.
195
www.eaton.com
EMR-3MP0
5 Recorders
5.1 Waveform Recorder