Core Power Solutions (DV2-C16 Models)
90
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
Step 1 – CS04-A11 placement and orientation
CS04-A11 current sensors must always be mounted onto the Live bus bar. (See
following diagram.)
Wherever possible, do not mount the CS04-A11 current sensor closer than 150mm
(6") from:
•
A bus bar joint
•
Termination bolts
•
Bolts joining laminated bus bars
Ensure correct orientation of the CS04-A11 current sensor before drilling the
mounting holes into the bus bar. (See following diagram.)
"
Live bus
#
To load or battery
$
To rectifiers
Step 2 – Drill the mounting holes
Drill two mounting holes according to the template below and tap if the threaded-
hole mounting option is used.
Through-hole
Threaded-hole
Drill
size
M3.5 M2.5
Thread size and
pitch
-
M3 x 0.5 ISO
Coarse