![Eaton DV2-C16-3 Series Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/eaton/dv2-c16-3-series/dv2-c16-3-series_installation-and-operation-manual_3839492095.webp)
Current Sensor Installation
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
89
Gain Range – for input inductor resistance values of …
90W 110W
120W
Jumper Configuration
16 – 21
13 – 18
12 – 16
19 – 29
16 – 24
15 – 22
27 – 52
22 – 42
20 – 39
38 – 132
31 – 108
29 – 99
40 – 160
33 – 130
30 – 120
The jumper connection points are located on the back of the CS04-A11 current sensor PCB.
To obtain the required jumper configuration, you might have to break the track between
connection points 1 and 3 and solder additional jumpers between connection points.
Step 5 – Apply heat sink compound as shown
"
Input inductor
#
Heat sink compound to ensure good thermal
contact between the input inductor and the busbar.
Procedure complete
Mounting the CS04-A11
The CS04-A11 is supplied with M3x35mm screws to attach the CS04-A11 current sensor to a
bus bar.
This section covers the following mounting options:
•
Through-hole mounting
•
Threaded-hole mounting