Start-Up
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
43
Parameter Action
SC200
Navigation*
Float Voltage
Set to the value recommended by
the battery manufacturer.
Control Processes > Voltage
Control > Float Voltage
Battery Capacity Set to the rated 10 hour capacity of
the installed battery strings. Zero
means no battery is installed.
Battery > Battery > Battery
Capacity
Cells Per String
Set to the number of cells in each
battery string.
Battery > Battery > Number of
Cells
Temperature
Compensation
Enable (if required) and check the
settings.
Control Processes >
Temperature Compensation >
Enabled
Low Voltage
Disconnect
(LVD)
Enable (if LVD installed) and
check the settings.
Battery > LVDs > LVD x
System
controller time
Connect using Web to set correct
time manually or connect using
DCTools to synchronize to PC
time. See details in the System
Controller Operation Handbook.
Web: Configuration > Time
DCTools: Configuration >
Identity > Time Synchronization
* Refer to the System Controller Operation Handbook for navigation details (see
Related Information on page
Other configuration settings can be changed after all Start-Up tasks are complete. Refer to the
System Controller Operation Handbook (see Related Information on page
) for details on
how to customize the system's configuration.
Task 5 - Apply DC Power to Battery and Load
Reverse Polarity
•
Always check that the battery cables have been terminated to the correct system polarity
BEFORE connecting the batteries or closing the battery disconnect device. Connecting batteries
to the dc power system with incorrect system polarity will damage the rectifiers and void all
warranty claims.
S
t
e
p
1
-
C
h
e
c
k
d
c
v
o
l
t
a
g
e
a
n
d
p
o
l
a
r
i
t
y
Check the dc output voltage and polarity of the power system and the
battery string(s).
Step 2 - Connect batteries
1
If connecting multiple battery strings then check the individual strings
are of similar voltage.
2
Switch on the battery circuit breaker(s) and/or fit the battery fuses.
3
Check the Battery Fuse Fail alarm clears.
4
Check the battery current. The actual value depends on the state of
charge of the batteries.