Checklists
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
85
Alarms (check as configured - typical examples may or may not apply)
Check ac utility fail condition
Check load low and high conditions
Check float low and high conditions
Check load fuse fail condition
Check rectifier urgent and non-urgent alarms
Check equalize/fast charge alarms
Check LVD alarms
Check summary alarms
Check alarm controls (beeps, latching, inhibit time, re-enable time)
Check auto external alarm reporting if installed
Check other alarms as configured
Check all alarm outputs as specified
Training and documentation
Operators and supervisors to obtain basic training and information for using the
supervisory module
Supervisors to obtain further training for reconfiguring they can do using
supervisory module
Operators and supervisors to obtain overview of documentation
Decide location of documentation — logbook, Configuration Printout, etc
Formal Acceptance
Signed acceptance sent to your Powerware dc product representative
Starting up records filed
Note in logbook and/or Configuration Printout
Note:
1
The Installer to upload and compare supervisory module configuration file using a PC
with the ICE Configuration Editor software.
2
Mark any differences in the Configuration Printout for the system, or reprint the full
configuration and place this in the Configuration Printout folder. If the supervisory
module’s configuration file is incorrect, you can download the correct configuration,
which should be available.
3
For more details, see Configuring the dc power system.
4
For details on using ICE, see the on-line help file (press F1).