For 2-pole and 3-pole circuit breakers (120-250A):
•
Replace the 1-pole live terminal insulators with a 2-pole or 3-pole
insulator as required.
•
Fit a 2-pole or 3-pole cable connection plate (vertical or horizontal)
to the circuit breaker terminals and common bar.
Step 3 - Install and terminate cables
1
Select cable sizes to suit the circuit breaker ratings (refer to following
table). Cable insulation must be minimum 90ºC (194ºF) rated.
2
Route the cables to the CPS.
3
Terminate the cables with the required crimp lugs (refer to the
following table).
CB Rating
(Note 1)
Cable Size
AWG
(Note 2)
2-hole Crimp Lug
(Note 3)
Crimping Tool
(Note 3)
5A
18
10A
16
15A
14
20A
12
25A
10
30A
10
YAV10-2TC14-FX Y8MRB-1
40A
8
YA8CL-2TC14-FX
50A
6
YAV6CL-2TC14-FX
60A
4
70A
4
80A
2
100A
1
120A
1
YAV4CL-2TC14-FX
Y1MRTC
150A
1/0
YAV25L-2TC38-FX
200A
4/0
YAV28L-2NT38-FX
250A
250
kcmil
YA31L-2TC38-FX
M29-11
Notes:
1
See circuit breaker part number and derating factors on page
2
Minimum cable size. Does not allow for excessive voltage drop in long cable runs at high
current.
3
Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or
equivalent UL-listed crimp lugs.