Core Power Solutions (DV2-C16 Models)
42
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
4
After start-up of the SC200:
•
Press any key to silence the alarm
Depending on the configuration file settings, the alarm LED(s) may be on and the SC200
will display some system alarm messages. This is normal. For an explanation of alarm
messages see Alarm Descriptions in the System Controller Operation Handbook.
•
The LCD display module shows the summary screen. See details in the System
Controller Operation Handbook.
If no load or battery is connected the current will be 0A.
•
If fitted and enabled, the LVD(s) operate.
5
Check for correct operation of the rectifier(s). Check only the green Power On LED(s) are
on (no alarm LEDs).
•
On the SC200 keypad select
Menu
>
Rectifiers.
See details in the System Controller
Operation Handbook. Check that all rectifiers are registered.
6
If any problems see Troubleshooting on page
. Otherwise switch on all remaining
rectifiers.
Task 4 - Configure the dc power system
The operational settings of the dc power system are stored in a configuration file loaded into
the SC200 system controller. Refer to the System Controller Operation Handbook for details
(see Related Information on page
).
The SC200 is supplied pre-loaded with a configuration file. If this configuration file has been
customized for the site then no further configuration changes will be necessary.
If the configuration file is not fully customized for the site then check the following settings
and change if necessary. It is important that these settings are correct before progressing
further.