IM05805016K
Page 29
Effective October 2007
Starting Conditions
Test Starting Conditions with a Jumper Between Terminal #11 and …
#28 - Remote Start (The engine will start)
#30 - Deluge Valve Start (The engine will start)
#31 - Mercoid Switch Input (The engine will start)
Note: To stop the engine, press the "OFF" button
Diesel Configuration Checklist
Confirm all settings below…
Date & Time
Weekly Run Timer
Run Period Timer
Pressure Start Point
Pressure Stop Point
Low Pressure Alarm
Pressure Deviation
Sequential Start Timer (If required)
Enable/Disable Manual Stop as per requirements
Enable/Disable AC Failure Start (If Required)
Print Routine (When finished at site set to 'Manual')
Set "Print Status Report" to YES.
Note: Press and hold the 'F3' button for 3 seconds in order to print a status report on controllers with firmware
version 4.6 or higher.
Before Leaving Site
Test printer by printing Status Report - and keep for your records.
Dump all printer messages contained in the memory.
(Hit time/print button for 3 seconds while printing - hold the reset button on printer until memory is
cleared).