Page 28
IM05805016K
Effective October 2007
Battery #1 Failure / Battery #2 Failure
Place the controller in the 'MANUAL' mode by depressing the "MANUAL" button
-Disconnect one of the leads going to battery #1
-'Battery #1 Failure' should illuminate after 3 minutes
-Reconnect Battery #1
Press the "OFF" button to reset the alarms
Place the controller in the 'MANUAL' mode by depressing the "MANUAL" button
-Disconnect one of the leads going to battery #2
-'Battery #2 Failure' should illuminate after 3 minutes
-Reconnect Battery #2
Press the "OFF" button to reset the alarms
Charger #1 Failure / Charger #2 Failure
Place the controller in the 'MANUAL' mode by depressing the "MANUAL" button
-Disconnect AC power going to the controller
-'Charger #1 Failure' and ' Charger #2 Failure' should illuminate after 3 minutes
-Reconnect AC power
Press the "OFF" button to reset the alarms
Fail to Start
Place the controller in the 'AUTO' mode by depressing the "AUTO" button
-Disconnect leads #9 & #10 going to the controller
-Start the controller either by jumpering remote start (Terminal #11 & #28) or by dropping the pressure
-After the controller goes through its cranking cycles 'Fail to Start' should illuminate
-Reconnect #9 & #10
Press the "OFF" button to reset the alarms
Optional Alarms
Place the controller in the 'MANUAL' mode by depressing the "MANUAL" button
Test Alarm Conditions with a Jumper Between Terminal #11 and … (If condition is used)
#16 - Low Fuel
#17 - High Fuel
#18 - Low Reservoir
#19 - High Reservoir
#20 - Fuel Spill
#21 - Low Room Temperature
#25 - Future #2
#24 - Future #2
#25 - Interlock (with jumper in engine should never start)
#29 - Low Suction
Note: To clear the above alarms, press the "OFF" button