Page 12
IM05805016K
Effective October 2007
12.2 Manual Start Test
12.3 Test Start Test
12.4 Weekly Exerciser Test
Depress the “Manual” button. The LED on the button will illuminate.
Fuel Solenoid relay will change state.
Press Crank No.1 pushbutton. Engine cranks and starts, “Engine Run” annunciator
illuminates.
Press “OFF” button. Wait for engine to stop. Push “Manual” button then press Crank
No.2 pushbutton. Engine cranks and starts, “Engine Run” annunciator illuminates.
Press “OFF” button. Engine will stop.
Depress the “Test” button. LED on button will illuminate.
Drain Valve Solenoid will energize and reduce pressure. Controller will start engine
automatically. “Engine Run” annunciator illuminates.
Press “OFF” button. Engine will stop.
NOTE:
Engine will stop if Low Oil Pressure, High Water Temp or
Overspeed alarms are detected.
Depress “OFF” button.
To test the Weekly Exerciser, preprogram the controller to initiate the test at a time
suitable to the user.
Depress “AUTO” button.
At programmed time and date the drain valve solenoid will open. When the pressure
drops below the start PSI value, engine will start, “Engine Run” annunciator will
illuminate, and drain valve solenoid will close.
Press “OFF” button. Engine will stop.
Reprogram Weekly Exerciser for normal operation.
NOTE:
Engine will stop if Low Oil Pressure, High Water Temp or
Overspeed alarms are detected.