IM05805016K
Page 11
Effective October 2007
12. Initial Start Up
1.
Ensure that circuit breakers CB1 and CB2 are in the OFF (0) position.
2.
Ensure that AC power is supplied to terminals L and N, and GD is grounded.
3.
Connect engine batteries to the controller, terminals 6,8 and 11. If batteries are connected in wrong polarity
the battery voltage will read zero.
Note that terminals 6A and 8A are for factory use only and NOT for external connections.
4.
Turn circuit breakers CB1 and CB2 ON (“1” position).
5.
Turn printer ON
after
CB1 and/or CB2 have been turned ON.
6.
Pressure (start) is factory preset at 1 PSI.
7.
Place the controller in the ‘OFF’ mode by depressing the “OFF” button.
8.
Ensure that the Diesel is programmed to user’s specifications. Refer to section 6 in this manual.
Refer to STATUS printout for factory set parameters.
12.1 Automatic Start Test
Test printer while in Auto mode as per Section 14 of manual.
Depress the “AUTO” button.
LED on “AUTO” button will light and Annunciator “Switch in Auto” will illuminate.
Ensure that water pressure is available and the LCD display on the Display Panel is
reading the system pressure, in PSI.
Decrease water pressure. Controller will begin its cranking cycle.
Should the engine fail to start after 6 crank and rest cycles, the audible alarm will
sound and the “Fail To Start” annunciator will illuminate. Depress “OFF” button to
silence alarm.
When engine starts, “Engine Run” annunciator illuminates.
Increase water pressure above programmed STOP point. Press the stop pushbutton on
the enclosure. If the pressure is satisfied, the engine will stop.
OR
If STOP mode is programmed for “Auto-Stop”, engine will stop after Run Period
Timer times out and pressure is satisfied. RPT is programmed by the user, factory set
at 30 minutes.
If Sequential Timer is > 0 seconds, automatic start will be delayed by the number of
seconds programmed.
If AC Power Failure is ENABLED, automatic start will be delayed by the number of
seconds programmed upon a power failure.