APPENDIX C: PRINTER ‘EVENT’ MESSAGES
Message
Description of Message
Message
** Print Out
Cranking Battery #1 or #2
Indicates which battery the controller is cranking during an
“attempt to start” cycle. This message will not print in the
manual mode.
MM/DD/YR, HH/MM/SS
Cranking Battery #X
**mode**
Drain Valve Opened
In the “TEST” mode or when initiating the weekly test timer
this message prints to indicate the actual time that the
drain valve has opened.
MM/DD/YR, HH/MM/SS
Drain Valve Opened
**mode**
Deluge Valve Open
Indicates that the engine was requested to start due to the
Deluge Valve being activated.
MM/DD/YR, HH/MM/SS
Deluge Valve Open
**mode**
Engine Run
Prints after the controller receives an “Engine Run” signal
from the diesel engine.
MM/DD/YR, HH/MM/SS
Engine Run
**mode**
Engine Stopped
Prints after the diesel engine has stopped as indicated by
the “Engine Run” contacts.
MM/DD/YR, HH/MM/SS
Engine Stopped
**mode**
Fuel Solenoid Closed
Any time the fuel solenoid is de-activated, after a manual
stop for example, this message will print.
MM/DD/YR, HH/MM/SS
Fuel Solenoid Close
**mode**
Fuel Solenoid Open
Any time the fuel solenoid is activated, prior to cranking for
example, this message will print.
MM/DD/YR, HH/MM/SS
Fuel Solenoid Open
**mode**
Low Pressure
This message is printed when the controller is called upon
to start the diesel engine as a result of low system
pressure.
MM/DD/YR, HH/MM/SS
Low Pressure
**mode**
Manual Stop Request
Indicates that the Local STOP pushbutton has been
depressed to initiate an engine shutdown.
MM/DD/YR, HH/MM/SS
Manual Stop Request
**mode**
Pressure = XXX PSI
Pressure reading will print if the deviation in pressure
exceeds the amount, in PSI, as programmed in to the
controller by the user.
MM/DD/YR, HH/MM/SS
Pressure = XXXPSI
**mode**
* Pressure Start
Future #2 relay will energize once the pressure is less
than the programmed Pressure Start Point and the engine
starts. Can be enabled or disabled.
MM/DD/YR, HH/MM/SS
Pressure Start
**mode**
Remote Start Request
Indicates that the engine was called upon to start due to
someone pressing the “Remote Start” pushbutton.
MM/DD/YR, HH/MM/SS
Remote Start Request
**mode**
RPT Time Out
After the Weekly Test Timer or Running Period Timer
expires (if STOP Mode is programmed for Auto) this
message will print.
MM/DD/YR, HH/MM/SS
RPT Timed Out
**mode**
Weekly Test Started
This is the actual time that the Weekly Test Timer is called
upon to start. The engine will continue to run for
30 minutes after the time indicated.
MM/DD/YR, HH/MM/SS
Weekly Test Started
**mode**
* Not Available on software versions V2.91 or earlier
** Mode ** refers to Main Switch Mode - AUTO, MANUAL, TEST