manualshive.com logo in svg
background image

 

 

 

IL04915001E

 

 

 

Effective 7/09 

 

 

Environment 

Operating temperature 

-35 

°

C to +60 

°

Storage temperature 

-40 

°

C to +80 

°

Humidity 

85% max (no condensation) 

Ingress protection 

IP20 

Shock resistance (no malfunction) 

10 G 

Vibration resistance (no malfunction) 

10 G, 10 – 55 Hz at 1.5 mm double amplitude 

 

Mechanical Properties 

Width 

45 mm 

1.77” 

Height 

70 mm 

2.76” 

Depth (not including terminal block) 

103 mm  4.03” 

Depth (including terminal block) 

126 mm  4.95” 

DIN rail if DIN rail mounted 

35 mm 

Screws if screw mounted 

M4 x 20  #8 x ¾”   (2 required) 

Weight (open) 

0.40 kg 

0.88 lbs. 

Weight (packaged) 

0.49 kg 

1.08 lbs. 

 

Applicable standards 

EN 61000-6-3 

Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission 
standard for residential, commercial and light-industrial environments (=lowest levels) 
30-230 MHz 

30 dB

µ

V at 10 m distance 

230-1000 MHz  37 dB

µ

V at 10 m distance 

EN 61000-6-2 

Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity 
standard for industrial environments (=highest levels) 
80-1000 MHz with 80% AM modulation up to 10 V/m at 3 m distance from source 

EN 61000-4-2 

Electromagnetic compatibility (EMC) for industrial-process measurement and control 
equipment – Part 4-2: Electrostatic discharge (ESD) immunity 

EN 61000-4-3 

Electromagnetic compatibility (EMC) for industrial-process measurement and control 
equipment – Part 4-3: Radiated electromagnetic field immunity 

EN 61000-4-4 

Electromagnetic compatibility (EMC) for industrial-process measurement and control 
equipment – Part 4-4: Electrical fast transient/burst immunity 

EN 61000-4-5 

Electromagnetic compatibility (EMC) for industrial-process measurement and control 
equipment – Part 4-5: Surge immunity 

EN 61000-4-6 

Electromagnetic compatibility (EMC) for industrial-process measurement and control 
equipment – Part 4-6: Conducted radio frequency field immunity 

EN 61000-4-11  Electromagnetic compatibility (EMC) for industrial-process measurement and control 

equipment – Part 4-11: Voltage dips/drops/variations immunity 

EN 60947-5-1 

Low-voltage switchgear and control gear – Part 5-1: Control circuit devices and 
switching elements – Electromechanical control circuit devices 

IEC 60755 

General requirements for Ground fault current operated protective devices 

UL 

UL 1053 Ground-Fault Sensing and Relaying Equipment, Class 1 

CSA 

C22.2 No. 144-M91 Ground Fault Circuit Interrupters 

CE 

CE mark – Declaration of Conformity 

 

Содержание Cutler-Hammer D64RPB30 Series

Страница 1: ...l contactor contacts in the case of S C faults In this case the unit does not trip initially when the measured current exceeds the S C setpoint but waits for the upstream device to take care of curren...

Страница 2: ...failed alarm state is As a result the red LED will now show the original cause of the trip 1 4 Reset Test pushbutton The built in momentary pushbutton is used to verify the condition of the D64RPB30 i...

Страница 3: ...ontrol voltage is removed the relay will issue a 0 2 0 3 second pulse This means that when control voltage is restored after a trip due to loss of control voltage the contact will remain open This avo...

Страница 4: ...ans that there is no electrical isolation between the control voltage input and the internal electronics As a result these share a common ground reference This reference is applied to the system throu...

Страница 5: ...stalled beside the unit to act as the chassis ground point Use a minimum 14 AWG stranded conductor 6 For good EMC behavior it is important as in any installation to run all wiring especially if unshie...

Страница 6: ...voltage 1 week minimum until the memory is read by pressing the Reset button Ground fault circuit G F Trip Level settable 0 03 0 10 0 50 1 2 3 5 9 A Accuracy of trip point 15 0 of Trip Level 3 G F Tri...

Страница 7: ...8 A2 28 mm 1 1 inner diameter External CT Supervision circuit CT loop resistance causing a fault O C 1 k CT shunt resistance causing a fault S C 50 CT Fault Trip Delay 1 5 s Relay contacts Configurati...

Страница 8: ...magnetic compatibility EMC for industrial process measurement and control equipment Part 4 2 Electrostatic discharge ESD immunity EN 61000 4 3 Electromagnetic compatibility EMC for industrial process...

Страница 9: ...OURCE CURRENT CARRYING NEUTRAL WHEN USED GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire LOAD FIGURE 2 D64RPB30 TYPICAL FIELD CONNECTION WITH EXTERNAL 500 1 CURRENT TRANSF...

Страница 10: ...1 38 35 2 36 60 2 76 70 1 38 35 Mounting hole Dia 0 22 5 5 DIN Rail Release 4 03 103 4 95 126 Dimensions Figure 3 Dimensions Drawing Approximate Dimensions in Inches mm Table 2 Approximate Dimensions...