manualshive.com logo in svg
background image

 

 

 

IL04915001E

 

 

 

Effective 7/09 

 

5. TECHNICAL SPECIFICATION 

Terminals 

Type 

Pull-apart 

UL/CSA rating 

300 V AC, 10 A 

VDE rating 

250 V AC, 12 A, pollution degree 3, over-voltage 
category III 

Insulation stripping length 

7 mm (0.27 “) 

Torque 

0.4 - 0.6 Nm (0.295 - 0.443 Ft. lb)  

Field wiring 

0.5 - 2.5 mm

2

 (VDE), 20 - 14 AWG (UL/CSA), Cu, solid or 

stranded 

Control power 

Voltage range 

Nominal:  24 – 240 V AC/DC, -20% / +10% 
Total: 

19.2 – 264 V AC/DC 

Frequency range on AC 

45 – 450 Hz 

Power consumption 

AC 1.5 VA max, DC 0.5 W 

Isolation voltage 

Not electrically isolated from electronics 

Loss of supply tolerance (no impaired 
operation) 

250 ms  at 24 V ac 
1 s 

at 120 V ac 

4 s 

at 230 V ac 

80 ms  at 24 V dc 
350 ms  at 48 V dc 
750 ms  at 110 V dc 

Power-up time 

500 ms for G/F detection 

2

   

100 ms for S/C detection 

System power 

Voltage range (using external CT) 

Any, providing the power conductors passing through the 
CT are insulated for the system voltage and electrical 
clearance requirements are met 

Current Range 

Maximum continuous phase current specified for the 
C311CT connected to the relay  

Frequency range 

45 – 450 Hz 

Memory after loss of control voltage 

1 week minimum (until the memory is read by pressing 
the Reset button) 

Ground fault circuit 

G/F Trip Level (settable) 

0.03, 0.10, 0.50, 1, 2, 3, 5, 9 A 

Accuracy of trip point 

-15% / +0% of Trip Level 

3

   

G/F Trip Delay (settable) 

 0.02. 0.30, 1, 2,  5, 10 s 

4

 

Accuracy of trip delay 

-2 / +5 ms or 

±

2.5% of Trip Delay, whichever is greater 

                                                

2

 

 

If a ground fault causing a current above the G/F Trip Level but below the S/C Trip Level is already present 

when power is applied, the system trips just as soon as possible, regardless of the G/F Trip Delay setting 
(rationale: the fault may have been present much longer than the delay set time and should be cleared without 
delay). 

3

 The accuracy of the trip point refers to the value of the real world ground fault current (assuming a purely 

sinusoidal wave shape) that just causes a trip when slowly increased from zero. 

4

 The ground fault detection mechanism has a ‘thermal’ behaviour for greatly reduced noise sensitivity: the 

quoted delays are valid for sinusoidal currents exceeding the setpoint by >10 times; for reduced current 
excursions the delay increases as follows: 
 

current = 6 x setpoint: 

add 3 ms 

 

current = 4 x setpoint: 

add 8 ms 

 

current = 2 x setpoint: 

add 20 ms 

 

current = 1.2 x setpoint:   add 60 ms 

For IEC 60755 ‘pulsating DC’ currents, the delay increases by a further 50 ms maximum. 

 

Содержание Cutler-Hammer D64RPB30 Series

Страница 1: ...l contactor contacts in the case of S C faults In this case the unit does not trip initially when the measured current exceeds the S C setpoint but waits for the upstream device to take care of curren...

Страница 2: ...failed alarm state is As a result the red LED will now show the original cause of the trip 1 4 Reset Test pushbutton The built in momentary pushbutton is used to verify the condition of the D64RPB30 i...

Страница 3: ...ontrol voltage is removed the relay will issue a 0 2 0 3 second pulse This means that when control voltage is restored after a trip due to loss of control voltage the contact will remain open This avo...

Страница 4: ...ans that there is no electrical isolation between the control voltage input and the internal electronics As a result these share a common ground reference This reference is applied to the system throu...

Страница 5: ...stalled beside the unit to act as the chassis ground point Use a minimum 14 AWG stranded conductor 6 For good EMC behavior it is important as in any installation to run all wiring especially if unshie...

Страница 6: ...voltage 1 week minimum until the memory is read by pressing the Reset button Ground fault circuit G F Trip Level settable 0 03 0 10 0 50 1 2 3 5 9 A Accuracy of trip point 15 0 of Trip Level 3 G F Tri...

Страница 7: ...8 A2 28 mm 1 1 inner diameter External CT Supervision circuit CT loop resistance causing a fault O C 1 k CT shunt resistance causing a fault S C 50 CT Fault Trip Delay 1 5 s Relay contacts Configurati...

Страница 8: ...magnetic compatibility EMC for industrial process measurement and control equipment Part 4 2 Electrostatic discharge ESD immunity EN 61000 4 3 Electromagnetic compatibility EMC for industrial process...

Страница 9: ...OURCE CURRENT CARRYING NEUTRAL WHEN USED GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire LOAD FIGURE 2 D64RPB30 TYPICAL FIELD CONNECTION WITH EXTERNAL 500 1 CURRENT TRANSF...

Страница 10: ...1 38 35 2 36 60 2 76 70 1 38 35 Mounting hole Dia 0 22 5 5 DIN Rail Release 4 03 103 4 95 126 Dimensions Figure 3 Dimensions Drawing Approximate Dimensions in Inches mm Table 2 Approximate Dimensions...

Отзывы: