IL04915001E

 

 

 

Effective 7/09 

 

10 

35 mm
DIN RAIL

LEFT HAND SIDE VIEW

REAR PANEL MOUNTING

D IN RAIL OR 2  SCREW

2.76 (70)

1.77 (45)

1.38 (35)

2

.3

6

 (

6

0)

2

.7

6

 (

7

0)

1

.3

8

 (

3

5)

Mounting
hole Dia
0.22“ ( 5.5)

DIN Rail
Release

4

.0

3

 (

1

0

3

)

4

.9

5

 (

1

2

6

)

 

 
 
Dimensions 

Figure 3. Dimensions Drawing – Approximate Dimensions in Inches (mm) 
 
Table 2. Approximate Dimensions and shipping weights 
 

Dimensions in Inches (mm) 

Shipping Weight 
lbs. (kg) 

Width 

Height 

Depth 

1.77 (45) 

2.76 (70) 

4.95 (126) 

1.08 (.49) 

 
 

Содержание Cutler-Hammer D64RPB30 Series

Страница 1: ...l contactor contacts in the case of S C faults In this case the unit does not trip initially when the measured current exceeds the S C setpoint but waits for the upstream device to take care of curren...

Страница 2: ...failed alarm state is As a result the red LED will now show the original cause of the trip 1 4 Reset Test pushbutton The built in momentary pushbutton is used to verify the condition of the D64RPB30 i...

Страница 3: ...ontrol voltage is removed the relay will issue a 0 2 0 3 second pulse This means that when control voltage is restored after a trip due to loss of control voltage the contact will remain open This avo...

Страница 4: ...ans that there is no electrical isolation between the control voltage input and the internal electronics As a result these share a common ground reference This reference is applied to the system throu...

Страница 5: ...stalled beside the unit to act as the chassis ground point Use a minimum 14 AWG stranded conductor 6 For good EMC behavior it is important as in any installation to run all wiring especially if unshie...

Страница 6: ...voltage 1 week minimum until the memory is read by pressing the Reset button Ground fault circuit G F Trip Level settable 0 03 0 10 0 50 1 2 3 5 9 A Accuracy of trip point 15 0 of Trip Level 3 G F Tri...

Страница 7: ...8 A2 28 mm 1 1 inner diameter External CT Supervision circuit CT loop resistance causing a fault O C 1 k CT shunt resistance causing a fault S C 50 CT Fault Trip Delay 1 5 s Relay contacts Configurati...

Страница 8: ...magnetic compatibility EMC for industrial process measurement and control equipment Part 4 2 Electrostatic discharge ESD immunity EN 61000 4 3 Electromagnetic compatibility EMC for industrial process...

Страница 9: ...OURCE CURRENT CARRYING NEUTRAL WHEN USED GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire LOAD FIGURE 2 D64RPB30 TYPICAL FIELD CONNECTION WITH EXTERNAL 500 1 CURRENT TRANSF...

Страница 10: ...1 38 35 2 36 60 2 76 70 1 38 35 Mounting hole Dia 0 22 5 5 DIN Rail Release 4 03 103 4 95 126 Dimensions Figure 3 Dimensions Drawing Approximate Dimensions in Inches mm Table 2 Approximate Dimensions...