background image

 

 

 

IL04915001E

 

 

 

Effective 7/09 

 

For the CT supervision feature to work a 500:1 
ratio Series A2 C311CT must be installed, as 
specified in section 5.  

1.3 LED indicators 

The unit has two LEDs. A green LED shows 
correct operation by slowly flashing (1 s on / 1 s 
off). When the unit is in a tripped condition, a red 
LED shows short 0.25 s flashes as a code 
indicating the cause of the trip: 

  One 0.25 s flash every few seconds means 

Ground fault current exceeded the set G/F 
limit, but did not reach S/C levels. This trip is 
labeled ‘G/F’. 

  Two consecutive 0.25 s flashes every few 

seconds means Ground fault current 
exceeded the S/C level. This trip is labeled 
‘S/C’. 
In case Type 2 Co-ordination is used, this 
code also means that the upstream device 
tripped correctly; after the current dropped to 
zero as a result of the upstream trip, the 
D64RPB30 activated its trip relay to isolate 
the faulty circuitry. 

  Three consecutive 0.25 s flashes every few 

seconds can only occur when Type 2 Co-
ordination is used. It means that Ground fault 
current exceeded the S/C level, but the 
upstream device failed to trip. The 
D64RPB30 then tripped as a last resort. This 
trip is labeled ‘Backup’. The contactor should 
be replaced since its contacts may have 
been damaged due to the S/C current. 

  Four consecutive 0.25 s flashes every few 

seconds means that the connection to the 
external CT is either open or shorted. Note 
that the trip is latched until reset; therefore 
intermittent failures will be captured, 
overcoming the impression that the unit 
tripped without cause. 

  Continuous 0.25 s flashes indicate an extra 

‘trip failed’ alarm state on top of one of the 
possible trips described above.  

Following the operation of the trip relay, 
measured ground fault current remained at a 
high level. When the local or remote reset 
button is first pressed, the trip is not reset, 
but the ‘trip failed’ alarm state is. As a result 
the red LED will now show the original cause 
of the trip. 

1.4 Reset / Test pushbutton 

The built-in momentary pushbutton is used to 
verify the condition of the D64RPB30 if control 
voltage has been removed from the relay (see 
section 1.5)

 

and to reset the internal relay and/or 

the red LED (depending on the exact Operating 
Mode, see section 1.6). 
The reset will only be granted if the cause of the 
trip is cleared. Otherwise the relay will remain 
activated without resetting. If the cause of the 
trip is cleared but another fault exists, then 
pressing the reset button will reset the trip 
indication on the red LED. This permits the new 
trip code to be displayed. However, the relay will 
remain activated without resetting. 
 
Double-clicking the local button invokes a test 
which switches an AC voltage onto the 
processor’s CT sensor input. The voltage is 
scaled to simulate a Ground fault current of 1.5 
times the G/F trip level setpoint. The unit will trip 
on G/F after the set delay (plus 0.4 s) and then 
switch off the AC voltage. Press the reset button 
again to reset the device. No external power 
supply is required. 

1.5 Memory after loss of control voltage 

When control voltage is removed from the 
D64RPB30, the condition of the relay will be 
memorized (for at least one week). Pressing the 
Reset pushbutton before restoring control 
voltage will light either the green LED or the red 
LED, green indicating no trip was registered and 
red indicating the opposite. The green LED will 
light continuously, whereas the red LED will give 
a sequence of short flashes as described in 
section 1.3 indicating the cause of trip. Please 
note that if the D64RPB30 is operated in one of 
the Failsafe modes (see section 1.6), and there 
was no trip when control voltage disappeared, 
the system will still activate its relay at the very 
moment of losing voltage. If this is what 
happened, the red LED will show five 
consecutive short flashes, meaning ‘relay was 
merely activated because control voltage was 
lost while operating in Failsafe mode’.  

Содержание Cutler-Hammer D64RPB30 Series

Страница 1: ...l contactor contacts in the case of S C faults In this case the unit does not trip initially when the measured current exceeds the S C setpoint but waits for the upstream device to take care of curren...

Страница 2: ...failed alarm state is As a result the red LED will now show the original cause of the trip 1 4 Reset Test pushbutton The built in momentary pushbutton is used to verify the condition of the D64RPB30 i...

Страница 3: ...ontrol voltage is removed the relay will issue a 0 2 0 3 second pulse This means that when control voltage is restored after a trip due to loss of control voltage the contact will remain open This avo...

Страница 4: ...ans that there is no electrical isolation between the control voltage input and the internal electronics As a result these share a common ground reference This reference is applied to the system throu...

Страница 5: ...stalled beside the unit to act as the chassis ground point Use a minimum 14 AWG stranded conductor 6 For good EMC behavior it is important as in any installation to run all wiring especially if unshie...

Страница 6: ...voltage 1 week minimum until the memory is read by pressing the Reset button Ground fault circuit G F Trip Level settable 0 03 0 10 0 50 1 2 3 5 9 A Accuracy of trip point 15 0 of Trip Level 3 G F Tri...

Страница 7: ...8 A2 28 mm 1 1 inner diameter External CT Supervision circuit CT loop resistance causing a fault O C 1 k CT shunt resistance causing a fault S C 50 CT Fault Trip Delay 1 5 s Relay contacts Configurati...

Страница 8: ...magnetic compatibility EMC for industrial process measurement and control equipment Part 4 2 Electrostatic discharge ESD immunity EN 61000 4 3 Electromagnetic compatibility EMC for industrial process...

Страница 9: ...OURCE CURRENT CARRYING NEUTRAL WHEN USED GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire LOAD FIGURE 2 D64RPB30 TYPICAL FIELD CONNECTION WITH EXTERNAL 500 1 CURRENT TRANSF...

Страница 10: ...1 38 35 2 36 60 2 76 70 1 38 35 Mounting hole Dia 0 22 5 5 DIN Rail Release 4 03 103 4 95 126 Dimensions Figure 3 Dimensions Drawing Approximate Dimensions in Inches mm Table 2 Approximate Dimensions...

Отзывы: