PUB 50411

 

 

D64RP18 SERIES B1 DIGITAL GROUND FAULT RELAY 

 

 

Revision 2 

May, 2005 

Page 8 

 

 

 

 

Refer to Figure 3 for mounting dimensions of the D64RP18 relay. It is designed to be mounted with 

either mounting screws or 35 mm DIN rail. 

 

 

Two #8-32 x 3/4" (M4 x 20) mounting screws are required for screw mounting. 

 

 

For DIN rail mounting the rail should be bolted to a flat surface. Install the DIN rail horizontally. Allow at 

least ¾” (20 mm) of rail to extend beyond each end of the relay. Secure the relay to the DIN rail 

ensuring the white release latch at the bottom of the relay engages the rail. If the relay is to be 

mounted in any other position take appropriate steps to prevent the relay from becoming disengaged 

from the DIN rail. 

 

3.2 

BUILT-IN CURRENT TRANSFORMER 

 

 

The D64RP18 has a built-in current transformer (CT) with 1.1” (28 mm) opening.  

 

 

Refer to Figure 1. Pass the phase conductors through the CT window. If the neutral conductor is 

carrying single phase current, it is to be passed through the window. Do not pass ground conductors 

through the CT window. In applications that require shielded wires to pass through the CT window, 

return the shields through the CT window before connecting them to ground. 

 

 

Verify that the polarity of the conductors is correct when they pass through the CT. Verify that ground 

paths do not exist that would bypass the CT.   

 

 

The D64RP18 Trip Level range is 30 mA to 6.0 Amps when using the built-in CT. The maximum 

continuous primary phase current is to be 100 Amps.  

 

3.3 

EXTERNAL CURRENT TRANSFORMER

 

 

 

Refer to the Glossary of Terms to determine if an external Current Transformer is required for the 

application. 

  

 

The D64RP18 will work with Eaton’s Cutler-Hammer C311CT current transformers having a turns ratio 

of 500:1. These are epoxy molded to give exceptional mechanical properties and have high-grade 

silicon iron cores for excellent coupling characteristics.  

 

 

Refer to section 4 to select the catalog number of the C311CT current transformer with the opening 

required for the application. 

 

 

Phase conductors must be insulated for the system voltage when it is higher than 660 Volts.  

 

 

Refer to Figure 2. Pass the phase conductors through the CT window. If the neutral conductor is being 

connected downstream, it is to be passed through the window. Do not pass ground conductors 

through the CT window. In applications that require shielded wires to pass through the CT window, 

return the shields through the CT window before connecting them to ground.  

 

 

Verify that the polarity of the conductors is correct when they pass through the CT. Verify that ground 

paths do not exist that would bypass the CT.   

 

 

Position power cables in the center of the current transformer opening. Keep cables and buswork clear 

of the split on split core current transformers. 

 

 

The two secondary terminals of the external CT are to be connected to terminals T1 and T2 of the 

D64RP18. 

 

3.4 

CONNECTIONS

 

 

 

All connections to the D64RP18 are by means of screw clamp terminals rated 10 Amps, 300 Volts. 

Terminals will accept #26-12 AWG solid or stranded conductors.  

 

Содержание Cutler-Hammer D64RP18

Страница 1: ...eration Eaton Electrical 3228 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 TEST RESET PUSHBUTTON N L POWER SUPPLY N O CONTROL CIRCUIT N C CONTROL CIRCUIT EXT...

Страница 2: ...TE 7 2 5 INDICATION 7 2 6 RESET 7 2 7 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 7 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 8 3 4 1 CON...

Страница 3: ...n on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transformer A Rule of Thumb for systems 600 Volts and lower The charging current is 0 5 Amp...

Страница 4: ...s restored the relay will trip and the green LED will resume fast blink after 500 milliseconds regardless of the time delay set on the Trip Delay DIPswitch and the above cycle will be repeated If the...

Страница 5: ...s 100 Amps continuous Any Eaton s Cutler Hammer C311CT with 500 1 ratio may be used when the above requirements dictate the use of an external CT The ground fault trip current setting range of 30 mA 6...

Страница 6: ...rrent exceeds the TRIP LEVEL setting the output relay changes state after the pre selected TRIP DELAY time 2 2 2 GROUND FAULT TRIP DELAY TIME DIPSWITCH 4 The ground fault TRIP DELAY time can be set at...

Страница 7: ...the unit After the trip if the external button is N O the trip mode is Non Failsafe the output relay will remain tripped and the green LED will fast blink until the button is pressed Manual Reset Afte...

Страница 8: ...maximum continuous primary phase current is to be 100 Amps 3 3 EXTERNAL CURRENT TRANSFORMER Refer to the Glossary of Terms to determine if an external Current Transformer is required for the applicat...

Страница 9: ...rrent transformer and a typical connection of an ac motor starter coil 1M A remote Reset button with N O contacts is connected to terminals R1 and R2 providing Non Failsafe operating mode Comparing th...

Страница 10: ...80 to 110 of rated voltage 24 240 V dc Under voltage tolerance no impaired operation withstands loss of supply up to 100 ms Power Up Time 500 milliseconds Maximum System Voltage Frequency 660 Volts a...

Страница 11: ...ms 19 35 ms 500 ms 546 579 ms 523 542 ms 512 529 ms 506 523 ms Ground Fault Trip Current Level 30 mA 6 0 Amps in 8 settings 30mA 120mA 210mA 300mA 600mA 2 4Amps 4 2Amps and 6 0Amps Setting within the...

Страница 12: ...ty EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN 61000 4 5 Electromagnetic compatibility...

Страница 13: ...R1 R2 PULSED AUTO RESET Closed Contacts on Terminals R1 R2 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME 4 CONTROL POWER...

Страница 14: ...CORE BALANCE 1M O L GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED R 1M 1M START STOP O L TRIP RESET DOUBLE CLICK FOR TEST...

Страница 15: ...AND PULSED TRIP AUTO RESET GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED ST DOUBLE CLICK FOR TEST T PULSED TRIP AUTO RESE...

Страница 16: ...IEW OPEN WEIGHT 0 88 LBS 40KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP18 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 3 58 91 1 38 35 2 7...

Страница 17: ...IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP18 AFTER GROUND FAULT TRIP TEST If the remote button is a N O device the D64RP18 is in the non failsafe...

Отзывы: