PUB 50411

 

 

D64RP18 SERIES B1 DIGITAL GROUND FAULT RELAY 

 

 

Revision 2 

May, 2005 

Page 5 

 

 

 

 

If control voltage is maintained on terminals N- & L+ after a ground fault trip, the RESET 

button must be pressed to reset the relay after clearing the ground fault. 

 

 

 

If control voltage is removed from terminals N- & L+ while a ground fault is detected, the 

output relay resets and the green LED is turned off.  

 

 

 

If the ground fault has not been cleared when control voltage is restored, the relay will trip and 

the green LED will resume fast blinking after 500 milliseconds, regardless of the time delay 

set on the Trip Delay DIPswitch. 

 

 

 

If the ground fault has been cleared when control voltage is restored, the relay will remain 

reset.  

 

  

 

The Non-Failsafe mode can be used when the output relay is operating undervoltage devices. 

This includes: contactor coils; starter coils; and circuit breakers equipped with UV trip coils. 

 

 

External Current Transformer: 

 

 

 

External current transformers (CTs) are required for any of the following applications: 

 

-

 

The size of the power conductors on which the D64RP18 is being applied is too large 

for the 1.1” built-in CT. 

 

-

 

The system voltage on which the D64RP18 is being applied is higher than 660 Volts. 

 

-

 

The system primary phase current on which the D64RP18 is being applied exceeds 

100 Amps continuous. 

 

 

 

Any Eaton’s Cutler-Hammer C311CT with 500:1 ratio may be used when the above 

requirements dictate the use of an external CT. The ground fault trip current setting range of 

30 mA – 6 Amps in 8 steps is the same. The maximum continuous primary phase current is to 

be 1000 Amps. 

 

 

 

The two secondary terminals of the external CT are to be connected to terminals T1 and T2 of 

the D64RP18. 

 

 

Chassis Ground 

 

 

 

Chassis ground is the ground to which all of the non-current carrying metal equipment is 

connected/bonded. Typically, equipment grounding is provided by means of a ground bus. A 

solid connection is to be made from terminal N- of the D64RP18 to the nearest chassis 

ground to ensure the relay complies with the specified Electromagnetic compatibility (EMC) 

standards. 

 

2.2 

DIPSWITCH SETTINGS

 

 

 

FOR MAXIMUM SAFETY THE SETTINGS DESCRIBED IN THIS SECTION SHOULD BE MADE 

WITH CONTROL VOLTAGE REMOVED FROM THE D64RP18 RELAY. 

 

 

The DIPswitches are mounted inside of the relay and are accessible through the front cover. It is 

recommended that all of the DIPswitches be set at one time.  

 

 

Should it be necessary to make changes to the DIPswitch settings when the D64RP18 relay is 

energized, this can be done without having any adverse effect on the performance of the relay. 

 

 

Please Refer to Table 1 on the next page. This provides a list of the 4 DIPswitches, the function of 

each group, and the values related to each setting. The DIPswitches are numbered from 1 to 4 bottom 

to top. 

Содержание Cutler-Hammer D64RP18

Страница 1: ...eration Eaton Electrical 3228 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 TEST RESET PUSHBUTTON N L POWER SUPPLY N O CONTROL CIRCUIT N C CONTROL CIRCUIT EXT...

Страница 2: ...TE 7 2 5 INDICATION 7 2 6 RESET 7 2 7 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 7 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 8 3 4 1 CON...

Страница 3: ...n on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transformer A Rule of Thumb for systems 600 Volts and lower The charging current is 0 5 Amp...

Страница 4: ...s restored the relay will trip and the green LED will resume fast blink after 500 milliseconds regardless of the time delay set on the Trip Delay DIPswitch and the above cycle will be repeated If the...

Страница 5: ...s 100 Amps continuous Any Eaton s Cutler Hammer C311CT with 500 1 ratio may be used when the above requirements dictate the use of an external CT The ground fault trip current setting range of 30 mA 6...

Страница 6: ...rrent exceeds the TRIP LEVEL setting the output relay changes state after the pre selected TRIP DELAY time 2 2 2 GROUND FAULT TRIP DELAY TIME DIPSWITCH 4 The ground fault TRIP DELAY time can be set at...

Страница 7: ...the unit After the trip if the external button is N O the trip mode is Non Failsafe the output relay will remain tripped and the green LED will fast blink until the button is pressed Manual Reset Afte...

Страница 8: ...maximum continuous primary phase current is to be 100 Amps 3 3 EXTERNAL CURRENT TRANSFORMER Refer to the Glossary of Terms to determine if an external Current Transformer is required for the applicat...

Страница 9: ...rrent transformer and a typical connection of an ac motor starter coil 1M A remote Reset button with N O contacts is connected to terminals R1 and R2 providing Non Failsafe operating mode Comparing th...

Страница 10: ...80 to 110 of rated voltage 24 240 V dc Under voltage tolerance no impaired operation withstands loss of supply up to 100 ms Power Up Time 500 milliseconds Maximum System Voltage Frequency 660 Volts a...

Страница 11: ...ms 19 35 ms 500 ms 546 579 ms 523 542 ms 512 529 ms 506 523 ms Ground Fault Trip Current Level 30 mA 6 0 Amps in 8 settings 30mA 120mA 210mA 300mA 600mA 2 4Amps 4 2Amps and 6 0Amps Setting within the...

Страница 12: ...ty EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN 61000 4 5 Electromagnetic compatibility...

Страница 13: ...R1 R2 PULSED AUTO RESET Closed Contacts on Terminals R1 R2 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME 4 CONTROL POWER...

Страница 14: ...CORE BALANCE 1M O L GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED R 1M 1M START STOP O L TRIP RESET DOUBLE CLICK FOR TEST...

Страница 15: ...AND PULSED TRIP AUTO RESET GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED ST DOUBLE CLICK FOR TEST T PULSED TRIP AUTO RESE...

Страница 16: ...IEW OPEN WEIGHT 0 88 LBS 40KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP18 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 3 58 91 1 38 35 2 7...

Страница 17: ...IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP18 AFTER GROUND FAULT TRIP TEST If the remote button is a N O device the D64RP18 is in the non failsafe...