PUB 50411

 

 

D64RP18 SERIES B1 DIGITAL GROUND FAULT RELAY 

 

 

Revision 2 

May, 2005 

Page 7 

 

 

2.4 

OUTPUT RELAY CONTACT STATE

 

 

The output relay contact state is determined by the operating mode selected and the sensing condition 

of the D64RP18 relay. This is shown in Table 2. Use this table when deciding on field connections. 

Refer to the CONNECTIONS section.  

 

2.5 

INDICATION

 

 

 

There is one green LED on the front of the D64RP18: 

 

 

 

Off: 

 

No control voltage or D64RP18 defective 

 

 

Slow Flashing:  Okay, control voltage on 

 

 

Fast Blinking: 

Ground Fault Trip 

 

 

Steady On: 

Control voltage too low or D64RP18 defective 

 

2.6 

RESET 

 

 

The D64RP18 has two terminals R1 and R2 for a remote N.O. Reset button. After a trip, the 

electronics remain in the tripped state until the ground fault has been cleared and the Reset button has 

been pressed, or the control voltage is removed from terminals L- & N+.  

 

 

It is 

NOT

 necessary to press the N.C. remote button after the ground fault has been cleared when the 

D64RP18 is set in the Pulsed Trip Auto Reset mode. In this mode the relay will reset automatically in 3 

seconds. 

 

2.7 

GROUND FAULT TEST 

 

Double clicking the external button connected to terminals R1 and R2 invokes a relay test. A simulated 

current equal to 1.2 times the trip current set on the Trip Level DIPswitches replaces the measured 

current. After the trip delay time set on the Trip Delay DIPswitch has elapsed, the unit should trip and 

the green LED will fast blink. This procedure tests the functionality of the unit. 

 

 

After the trip, if the external button is N.O. (the trip mode is Non-Failsafe), the output relay will remain 

tripped and the green LED will fast blink until the button is pressed (Manual Reset)   

 

 

After the trip, if the external button is N.C. or there is a jumper on terminals R1 and R2 (the trip mode is 

Pulsed Trip Auto Reset), the output relay will reset and the green LED will revert to slow flash 3 

second after the test was invoked (Auto Reset) 

 

 

A “Test Record Form” is included in this instruction manual. This form provides spaces to record the 

date the test was performed and the results. Those in charge of the building’s electrical installation 

should retain the form in order to be available to the authority having jurisdiction. 

 

 3. 

INSTALLATION INSTRUCTIONS

 

 

Place the D64RP18 in a clean dry enclosure. Try to keep the exposure to mechanical shock and 

vibration to a minimum, even though the internal electronics have been encapsulated in epoxy to 

improve the performance in high vibration environments.  

 

Locate the relay close to the isolating device (circuit breaker or contactor) that is protecting the circuit 

being monitored. If using an external CT keep the distance between the relay & CT as short as 

possible.

 

 

Provide maximum clearance between the D64RP18 (and the external CT if being used) and any 

strong magnetic flux producing devices such as power transformers, autotransformers, control 

transformers, reactors, and high power conductors and buswork.  

 

CAUTION: For reliable ground fault detection by the D64RP18 use one CT configuration only: Built-in 

CT; or, External CT (i.e. do not pass power conductors through the built-in CT when using an 

external CT.) 

3.1 

MOUNTING 

Содержание Cutler-Hammer D64RP18

Страница 1: ...eration Eaton Electrical 3228 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 TEST RESET PUSHBUTTON N L POWER SUPPLY N O CONTROL CIRCUIT N C CONTROL CIRCUIT EXT...

Страница 2: ...TE 7 2 5 INDICATION 7 2 6 RESET 7 2 7 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 7 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 8 3 4 1 CON...

Страница 3: ...n on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transformer A Rule of Thumb for systems 600 Volts and lower The charging current is 0 5 Amp...

Страница 4: ...s restored the relay will trip and the green LED will resume fast blink after 500 milliseconds regardless of the time delay set on the Trip Delay DIPswitch and the above cycle will be repeated If the...

Страница 5: ...s 100 Amps continuous Any Eaton s Cutler Hammer C311CT with 500 1 ratio may be used when the above requirements dictate the use of an external CT The ground fault trip current setting range of 30 mA 6...

Страница 6: ...rrent exceeds the TRIP LEVEL setting the output relay changes state after the pre selected TRIP DELAY time 2 2 2 GROUND FAULT TRIP DELAY TIME DIPSWITCH 4 The ground fault TRIP DELAY time can be set at...

Страница 7: ...the unit After the trip if the external button is N O the trip mode is Non Failsafe the output relay will remain tripped and the green LED will fast blink until the button is pressed Manual Reset Afte...

Страница 8: ...maximum continuous primary phase current is to be 100 Amps 3 3 EXTERNAL CURRENT TRANSFORMER Refer to the Glossary of Terms to determine if an external Current Transformer is required for the applicat...

Страница 9: ...rrent transformer and a typical connection of an ac motor starter coil 1M A remote Reset button with N O contacts is connected to terminals R1 and R2 providing Non Failsafe operating mode Comparing th...

Страница 10: ...80 to 110 of rated voltage 24 240 V dc Under voltage tolerance no impaired operation withstands loss of supply up to 100 ms Power Up Time 500 milliseconds Maximum System Voltage Frequency 660 Volts a...

Страница 11: ...ms 19 35 ms 500 ms 546 579 ms 523 542 ms 512 529 ms 506 523 ms Ground Fault Trip Current Level 30 mA 6 0 Amps in 8 settings 30mA 120mA 210mA 300mA 600mA 2 4Amps 4 2Amps and 6 0Amps Setting within the...

Страница 12: ...ty EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN 61000 4 5 Electromagnetic compatibility...

Страница 13: ...R1 R2 PULSED AUTO RESET Closed Contacts on Terminals R1 R2 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME 4 CONTROL POWER...

Страница 14: ...CORE BALANCE 1M O L GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED R 1M 1M START STOP O L TRIP RESET DOUBLE CLICK FOR TEST...

Страница 15: ...AND PULSED TRIP AUTO RESET GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED ST DOUBLE CLICK FOR TEST T PULSED TRIP AUTO RESE...

Страница 16: ...IEW OPEN WEIGHT 0 88 LBS 40KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP18 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 3 58 91 1 38 35 2 7...

Страница 17: ...IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP18 AFTER GROUND FAULT TRIP TEST If the remote button is a N O device the D64RP18 is in the non failsafe...

Отзывы: