PUB 50411

 

 

D64RP18 SERIES B1 DIGITAL GROUND FAULT RELAY 

 

 

Revision 2 

May, 2005 

Page 4 

 

 

 

Pulsed (Trip) Auto Reset: 

 

 

 

Each time control power is applied, the internal processor of the D64RP18 selects this mode 

when it sees a closed circuit on terminals R1 & R2 (there is a jumper or a N.C. pushbutton 

connected to R1 and R2). In this mode the N.C. button does not perform a reset function. 

 

 

 

The output relay N.O. contact is closed when tripped and the N.C. contact is open when 

tripped. 

 

 

 

The output relay does not change state when control power is applied to terminals N- & L+.  

 

 

 

 

With control voltage on terminals N- & L+ (Green LED slow flashing), when the measured 

values reach or exceed the DIPswitch settings for current and time, the output relay changes 

state (trips) and the green LED changes to fast blinking. The output relay will remain tripped 

until one of the following conditions is met: 

 

-

 

Three seconds after the ground fault current drops below the trip current set point the 

relay will reset and the green LED resumes slow flashing. This is, in effect, pulsed 

Auto Reset. 

 

-

 

If the control voltage is removed by the trip action of the output relay (i.e. it operates 

the shunt trip of the breaker that is providing the control voltage), the relay will reset 

with a short delay and the green LED is turned off. This is, in effect, Auto Reset. 

 

 

 

If the ground fault has not been cleared when control voltage is restored, the relay will trip and 

the green LED will resume fast blink after 500 milliseconds, regardless of the time delay set 

on the Trip Delay DIPswitch, and the above cycle will be repeated. 

 

 

 

If the ground fault has been cleared when control voltage is restored, the relay will remain 

reset.  

 

 

 

The Pulsed Trip Auto Reset mode can be used when the application calls for Auto Reset. 

 

 

 

The Pulsed Trip Auto Reset mode is designed for applications where the output relay is 

operating a shunt trip device. The D64RP18 resets automatically 3 seconds after the ground 

fault current is interrupted by the tripping action of the circuit breaker. The output contact to 

the shunt trip coil opens. This prevents damage to the internal mechanism of the circuit 

breaker in the event that the operator tries to reset the circuit breaker. When the control 

voltage to the D64RP18 is interrupted by action of the shunt trip, the D64RP18 resets with a 

short delay. 

 

 

  

Non-Failsafe: 

 

 

 

Each time control power is applied, the internal processor of the D64RP18 selects this mode 

when it sees an open circuit on terminals R1 & R2 (there is no contact or a N.O. pushbutton is 

connected to R1 and R2).  

 

 

 

The output relay N.O. contact is closed when tripped and the N.C. contact is open when 

tripped. 

 

 

 

The output relay does not change state when control power is applied to terminals N- & L+. 

  

 

 

With control voltage on terminals N- & L+ (Green LED slow flashing), when the measured 

values reach or exceed the DIPswitch settings for current and time, the output relay changes 

state (trips) and the green LED changes to fast blinking.  

 

Содержание Cutler-Hammer D64RP18

Страница 1: ...eration Eaton Electrical 3228 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 TEST RESET PUSHBUTTON N L POWER SUPPLY N O CONTROL CIRCUIT N C CONTROL CIRCUIT EXT...

Страница 2: ...TE 7 2 5 INDICATION 7 2 6 RESET 7 2 7 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 7 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 8 3 4 1 CON...

Страница 3: ...n on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transformer A Rule of Thumb for systems 600 Volts and lower The charging current is 0 5 Amp...

Страница 4: ...s restored the relay will trip and the green LED will resume fast blink after 500 milliseconds regardless of the time delay set on the Trip Delay DIPswitch and the above cycle will be repeated If the...

Страница 5: ...s 100 Amps continuous Any Eaton s Cutler Hammer C311CT with 500 1 ratio may be used when the above requirements dictate the use of an external CT The ground fault trip current setting range of 30 mA 6...

Страница 6: ...rrent exceeds the TRIP LEVEL setting the output relay changes state after the pre selected TRIP DELAY time 2 2 2 GROUND FAULT TRIP DELAY TIME DIPSWITCH 4 The ground fault TRIP DELAY time can be set at...

Страница 7: ...the unit After the trip if the external button is N O the trip mode is Non Failsafe the output relay will remain tripped and the green LED will fast blink until the button is pressed Manual Reset Afte...

Страница 8: ...maximum continuous primary phase current is to be 100 Amps 3 3 EXTERNAL CURRENT TRANSFORMER Refer to the Glossary of Terms to determine if an external Current Transformer is required for the applicat...

Страница 9: ...rrent transformer and a typical connection of an ac motor starter coil 1M A remote Reset button with N O contacts is connected to terminals R1 and R2 providing Non Failsafe operating mode Comparing th...

Страница 10: ...80 to 110 of rated voltage 24 240 V dc Under voltage tolerance no impaired operation withstands loss of supply up to 100 ms Power Up Time 500 milliseconds Maximum System Voltage Frequency 660 Volts a...

Страница 11: ...ms 19 35 ms 500 ms 546 579 ms 523 542 ms 512 529 ms 506 523 ms Ground Fault Trip Current Level 30 mA 6 0 Amps in 8 settings 30mA 120mA 210mA 300mA 600mA 2 4Amps 4 2Amps and 6 0Amps Setting within the...

Страница 12: ...ty EN 61000 4 4 Electromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 4 Electrical fast transient burst immunity EN 61000 4 5 Electromagnetic compatibility...

Страница 13: ...R1 R2 PULSED AUTO RESET Closed Contacts on Terminals R1 R2 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME 4 CONTROL POWER...

Страница 14: ...CORE BALANCE 1M O L GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED R 1M 1M START STOP O L TRIP RESET DOUBLE CLICK FOR TEST...

Страница 15: ...AND PULSED TRIP AUTO RESET GROUNDED SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED ST DOUBLE CLICK FOR TEST T PULSED TRIP AUTO RESE...

Страница 16: ...IEW OPEN WEIGHT 0 88 LBS 40KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP18 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 3 58 91 1 38 35 2 7...

Страница 17: ...IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP18 AFTER GROUND FAULT TRIP TEST If the remote button is a N O device the D64RP18 is in the non failsafe...