FEATURES 

 

Actuator for one (1x) electric strike through a monostable relay 

 

Encrypted communication with  the  access control device during the 
opening  of  the  door,  either  via  serial  communication  or  through  a 
secure KNX object (depending on the access control device) 

 

Supports KNX Data Security 

 

Manual output operation with push button and LED status indicator 

 

Auxiliary power supply required 

 

Total data saving on power failure 

 

Integrated KNX BCU (TP1-256) 

 

Dimensions 67 x 90 x 36 mm (2 DIN units) 

 

DIN rail mounting (IEC 60715 TH35), with fixing clamp 

 

Conformity with CE, UKCA, RCM directives (marks on the right side) 

 

  

 

1. Pairing button 

2. Pairing LED 

3. Auxiliary power 

supply 

4. Electric strike 

output 

5. Encrypted communication 

6. Output status 

LED 

7. Output control button 

8. Programming/Test button 

9.   Programming/Test LED 

10. KNX connector 

11. Fixing clamp 

Figure 1: Securel v3 

PROGRAMMING/TEST BUTTON: short button press to set programming mode. If this button is held while connecting the device to the auxiliary power 
supply, it enters the safe mode. If this button is held for more than 3 seconds, the device enters the test mode. 
PROGRAMMING/TEST LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual 
mode is indicated by the green color. During the start-up (after reset or power failure) and if the device is not in safe mode, it emits a red flash. 
PAIRING BUTTON: holding this button for more than three seconds will activate the pairing mode and delete the previous one in case the device was 
paired before. 
PAIRING LED: the LED will flash in blue colour while the device is unpaired. Once paired, the LED remains off. 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

2.8 

81.2 

24 VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

External power supply 

24 VDC. Maximum consumption: 13 mA 

Operation temperature 

0 .. +55 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class 

III 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on external power supply failure 

Data saving according to parameterization 

Response on external power supply restart 

Data recovery according to parameterization 

Operation indicator 

The programming LED indicates programming mode (red) and test mode 
(green). The output LED indicates its status (green). The pairing LED will 
flash in blue while the device is unpaired. 

Weight 

79 g 

PCB CTI index 

175 V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

10 

11 