40
Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
7 Operating
Overview:
Main menu
Test & Statusmenu
Block & Reset Alarms
Basic setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & Time
Functiontest
Durationtest
Delaytime Mains Ret.
Manual reset
Relay setup
Buzzer setup
Display setup
Charger setup
Webserver-Setup
Timer setup
Group device Setup
Connection to BMS
Function keys
Optional input
Serialnumber & Type
Password protection
Daylight saving time
Service info
Selection of the
menu points
with the keys
<ok>:
confirm
selection
<Menu>: Exit
and return to
previous menu
(with input of
any changes
made)
<ESC>: Exit
and return to
previous menu
(without input
of any changes
made)
flashing input
prompt
Relay module setup
Webserver-Setup
Timer setup
Group device Setup
etc. ...
<ok>
Menu 3.13:
Search group devices ...
Groupnumber: 07
Group devices
S1/S2-Mode: Slave
S3/S4-Mode:------
*
<Menu> ends the entry; the
following message appears:
Device address: 01
Version Z410C
ND 00 09 73 72 96 00
Name of station
The selection in the (second) menu serves to display the sub-stations available. Only sub-
stations with a pre-set group number are selected; otherwise the error message “Transmission
Fault” appears. Using the selection “S1/S2 mode: Master” the whole group can be switched to
“Blocked” mode using the F3 switch in the master control unit. The display in the master control
unit then shows “Blocked S1/S2” - the message “Blocked LON” then appears on the screens of
the control units in the sub-stations
Possible settings:
S1/S2: Slave or Master or ------
S3/S4: Slave or Master or ------
Explanation:
Slave: obeys Master
------: does not obey Master
Master: sends to Slaves and is simultaneously Slave
<ok>
Menu 3.14:
Using this menu the system is activated
and connected to a superior monitoring
system via CG-S bus or by using the M3
function.
Line selection (1 to 2) with
Select a device (bus) address
(1 ... 32) in line 1 with the keys
(display -- : no connection)
Select No/Yes in line 2 for the LON
switch option with
Line 4: Name of the station can be
freely defined. See text-assignment
4.3
Exit and return to Menu 3 with
<Menu>
Note:
The entries in lines 3 and 4 serve as
Information for the systems integrator.
Systemaddress: 1
LON-switches No
NID00 05 94 75 52 00
Name of station
Webserver-Setup
Timer setup
Group device Setup
Connection to BMS
etc. ...
Timer setup
Group device Setup
Connection to BMS
Function keys
etc. ...
<ok>
Menu 3.15:
Function key
1
No function
Switch
Block device
Sim.mainsfailuresubDB
Reset ISO-failure
Manual reset
Reset DeepDischarge
FT without forerun
Show sumfailures
Maintained off
non maintained on
Using this menu point the function keys (F1
... F3 in the control unit) can be allocated to
functions that are immediately carried out
when the relevant key is clicked.
Naturally, one function only can be assigned
to a key; the asterisk disappears if a
different function is allocated to a key.
Selection of function key (1 to 3) with
the keys
Select the function with
Select the function (
) with the <ok>
key
Exit and return to Menu 3 with
<Menu>