Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
Important information
F1-0 2,5A
T F2-0 2,5A
T F3-0 2,5A
T F4-0 2,5A
T
F1-U 2,5A
T F2-U 2,5A
T F3-U 2,5A
T F4-U 2,5A
T
Connection for digital inputs:
8 freely assignable 230V digital inputs for:
• Switch
• Switch inverted
• Start / exit function test
• Start / cancel duration test
• Block / unblock system
• Manual reset
• Switch maintained light on/off
t > 300 ms
t > 300 ms
Connection for 230V digital inputs
8 freely assignable 230V inputs for, e.g. external switch
inverted, switch, start / cancel function test, start / cancel
duration test, manual reset, switch maintained light on/off,
switch emergency lighting on as corridor lighting.
Tabelle 1: Optional inputs Z1 - Z8
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
Comments
No function
–
Factory setting
External switch
Level control via switch
230 V AC = ON
0 V = OFF
Works as switch and switches the circuit or
LED(s) with “S” function.
External switch inverted
Level control via switch
230 V AC = OFF
0 V = ON
Manual reset
Flank control via a button
LOW – HIGH
To reset the switch type “Manual reset”.
Reset DeepDischarge
Reset the total discharge protection.
Start functiontest
Trigger function test.
Start durationtest
Trigger duration test.
Cancel function test / duration test
Cancel function test and duration test.
Block device
Block mains / emergency light function during
operational rest periods.
Switch off maintained light
All LEDs / electric circuits that were previously
programmed in maintained light mode are
switched off.
Switch standby lighting on
All luminaires / electric circuits that were pre-
viously programmed in standby lighting mode
are switched on.
Ventilator monitoring
Level control via switch
230V AC = OK
0 V = disruption
Offsets a charge fault from the CG IV /CG V
relay module and CG Vision via the potential-
free signalling contact in the control unit,
insofar as there are 0V.
External ISO monitor
External battery monitor
External monitor
Level control:
Flank control: