![Eaton CEAG LP-STAR Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/eaton/ceag-lp-star/ceag-lp-star_mounting-and-operating-instructions_3833622034.webp)
34
Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
7 Operating
7 .4 .1 Menu 1: “Test & Statusmenu”
<ok>
Menu 1.1:
<ok> triggers a function test for the
linked final circuit:
The default message “Function Test”
appears in the LC display.
After programmable mains period (15 s to
900 s) a battery test is carried out (approx.
<ok>
Menu 1.2:
<ok> triggers a duration test:
The default message “Durationtest”
and the duration of the test (up to a
programmed nominal operating time)
appear in the graphic display. (see Menu
3.17 <<Serialnumber & Type>>)
<ok>
Menu 1.3:
<ok> triggers the termination of the
current duration test:
The default display appears once again
with information on the current system
operations.
3 min.). If a fault is registered an error
message appears in the default display.
In the following sub-menus in the Test &
Statusmenu (“1.4 Sum failure info” etc.)
further information can be found.
If the programmed nominal operating time
(see Menu 3.17 “Serialnumber & Type”) is
not reached, the message “Load/Battery
Fault” appears in the default display.
In this case the the battery pack must be
checked and changed if necessary!
Sum failures
Fault 1
Fault 2
Fault 3,
etc.
Start functiontest
Start durationtest
Cancel durationtest
ISO monitor test
etc.
Start functiontest
Start durationtest
Cancel durationtest
ISO monitor test
etc.
Start durationtest
Cancel durationtest
ISO monitor test
Sum failure info
etc.
Overview:
Main menu
Test & Statusmenu
Block & Reset Alarms
Basic setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 1
Start functiontest
Start durationtest
Cancel durationtest
ISO monitor test
Sum failure
Circuit-state
Luminaire-state
DLS/TLS/3Ph-state
Charging-/Bat.state
Relay-state
Group device state
Selection of the
menu points with
the keys
<ok>:
confirm selection
<Menu>: Exit
and return to
previous menu
(with input of any
changes made)
<ESC>: Exit
and return to
previous menu
(without input
of any changes
made)
flashing input
prompt
Step-by-step questioning with
If several error messages these can be
displayed in the graphic display on a step-
by-step basis.
<ok>
Menu 1.5: Shows the list of error
messages
Start functiontest
Start durationtest
Cancel durationtest
ISO monitor test
etc.
<ok>
Menu 1.4:
<ok> the following text appears if the
device is in battery mode:
By pushing the OK butten in the respective
line, an appropriate failure is generated,
which is displayed as „Isolation failure“ in
the last line. If the test failes, the text „ISO
monitor failure“ is displayed in the last line.
If this display appears, the battery mode
has to be started by the operator (e.g. FT,
DT, mains failure).
ISO monitor test
ISO-F
ISO-Failure –
___________
ISO monitor test
not possible at
actual state !!!
Continue With MENU
Start durationtest
Cancel durationtest
ISO monitor test
Sum failure
etc.