Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
Important information
9
128 x 64 Pixel graphic display, back-lit, contrast and brightness
adjustable via the program
10
3 keys for: Test (power failure, battery operations), function test,
duration test
11
3 freely assignable function keys
12
7 steering keys for user-friendly navigation
13
Connection for optional web module
*Connection for potential-free signalling contact,
24v 0 .5 A (SELV):
4 relays with own potential, each 1x switch-over contact.
Every potential-free contact can have one or more of 11
different alerts assigned to it. Freely programmable, DIN
VDE specification retrievable at any time as default setting.
Freely programmable control unit
with non-volatile program memory for programming and
user-specific parametrisation.
Internal log book recording
The control unit records the log book (max. 3,000 entries) in
accordance with the specifications of DIN VDE 0108. External
storage via the memory card is possible.
Operation
• at the front of the device
The device and the lighting system are operated on a
menu-supported basis via
• the keyboard and
• 128 x 64 Pixel graphic display, back-lit, contrast and
brightness adjustable via the program, (see Chapter 7).
Configuration
• at the front of the device
via keyboard and graphic display There are numerous
possibilities for user-defined settings via menu operated
parametrisation (see Chapter 7).
• by means of data exchange
via memory card, e. g. for the transfer of the settings
between similar LP-STAR devices.
• external configuration of the control unit is possible by
means of
• a standard PC and
• PC programming software
3 .6 Overview of the structural components
3 .6 .1 Control unit
Connections
• Plug connector clips for easy assembly disassembly. All
the connections are carried out using the plug connector
clips (see page ??, detailed view, as well as Appendix A:
“Connections”)
• Bus lines
4 x 2 x 0.8 mm
2
type: JY(ST)Y, twisted pair shielded
(minimum requirement).
• Connection for potential-free signalling contact, 24v 0.5 A:
4 relays with own potential, each 1x switch-over contact.
Every potential-free contact can have one or more of 11
different alerts assigned to it. Freely programmable, DIN
VDE specification retrievable at any time as default setting.
The terminal units on the module serve to simplify the
assembly and disassembly of the module; the connections
are positioned on plug in screw terminals.
F1-0 2,5A
T F2-0 2,5A
T F3-0 2,5A
T F4-0 2,5A
T
F1-U 2,5A
T F2-U 2,5A
T F3-U 2,5A
T F4-U 2,5A
T
1
2
4
3
5
11
12
13
8
10
7
6
9
1
CG-S bus connector CGVision, 24V supply voltage, potential-free
signalling contacts, 24V current loop for external voltage gauges*
2
8 freely assignable 230V digital inputs
3
3-phase feeding into the network with integrated phase monitoring
function.
4
Four end circuits depending on the model of the device for the
connection of the emergency lighting.
5
Mains fuse 6.3 AT
6
Circuit fuse 2.5 AT
7
SD card slot
8
Status LED display