32
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Installation
Fixing Details
Read all the installation instructions before commencing with the installation .
The installation of this panel must be carried out by a suitably
qualified /trained person .
The installation must comply with IEE wiring regulations and with
BS5839 part 1 and part 6 .
The electronic components within the fire panel are Static Sensitive .
Do not touch the electronics directly .
Mounting the Backbox
The panel can be flush mount or surface mounted .
1. For Surface Mount; drill four holes and fix the backbox to the wall.
2. For Flush Mount the backbox requires a hole 310mm x 355mm with a depth
of 117mm.
Figure 2 . Back Box dimensions
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables
and fit the glands .