Compatible Equipment
The range of compatible detectors for the CF2000 system consists of the following:
Model
optical sensor
Heat sensor
opto-Heat
sensor
Operating voltage
18 to 30V dc
Standby current (max)
220μA
Alarm current (max)
5mA
Ambient Temperature (max)
60ºC
A1R
50ºC
50ºC
BS
65ºC
CS
80ºC
Ambient Temperature (min)
-20ºC
Alarm temperature (static)
N/A
A1R
60ºC
60ºC
BS
77ºC
CS
90ºC
Heat sensor class as defined by
EN54-5:2000
N/A
A1R, BS, CS
control panel
selectable
A2S
Relative humidity (no n co nd)
0 to 95%
Height (w/o base)
34mm
43mm
Height (with base)
47mm
56mm
Diameter
100mm
Weight (w/o base)
86g
78g
76g
Material
PC/ABS
Colour
White
Optical Sensor
This is the most commonly used detector
and is most suitable for detecting slow
burning fires .
The status LED can be programmed to
either be permanently off under normal
conditions or to pulse in order to confirm
that it is in communication with the
control panel .