Commissioning the panel
Device input programming
•
Fire = panel reports fire from device .
•
Fault = panel reports fault from device .
•
Reset = panel resets .
•
Silence = silence all currently active sounders .
•
Technical/Input = No indication on display, creates a log entry .
•
Evacuate = Sends an evacuation command .
•
Fire/Extinguisher Activate = German mode only .
•
FRE Activate = German mode only .
•
None Fire = No indication on display, creates a log entry .
•
Cascade = Selects a delay in seconds on the device within the list This will go to
alarm after the selected time so can be used as a further trigger source .
•
Isolate Addresses = This allows a group of addresses (max 8 on the same loop) to
be isolated from the trigger . Panel does not go to Fire, trigger is non-latching
•
Isolate Zones = This allows a group of zones (max 8) to be isolated from the
trigger . Panel does not go to Fire, trigger is non-latching
Non-Latching
Non-latch is a feature where the panel goes back into quiescent state when the Fire
situation is cleared .
Day / Night
Devices affected:
•
Optical-Heat – mode changes between heat or opto-heat mode .
•
Heat – mode changes between Heat A1R and Head CS .
Allocate Zones/Devices
User can define between zones or addresses to be isolated on activation of the
device . The isolate list button enables the user to enter upto 8 unique zones or
addresses .