Technical Specification
outputs
Conventional sounder circuits
Nominal Voltage
20.4V - 29.0V
Number of sounder circuits
4
Total Sounder Load
1.0A (FH1204)
Maximum Sounder Circuit Load
800mA
Sounder Circuit Fuses (F1/2/3/4)
1.6A (Quick Blow)
End of line resistor
6k8
Fire routing equipment
Nominal Voltage
20.4V - 29.0V
Max Load
60mA
Fused (PTC2)
100mA polyswitch
End of Line resistor
6k8
Max Cable Length
2km
Min Recommended cable size (csa)
1mm
2
Fire Protecting equipment
Nominal Voltage
20.4V - 29.0V
Max Load
60mA
Fused (PTC4)
100mA polyswitch
End of Line resistor
6k8
Max Cable Length
2km
Min Recommended cable size (csa)
1mm
2
Fault routing equipment
Input Voltage
30V
Input Current
30mA
Fused (PTC1)
100mA polyswitch
End of Line resistor
6k8
Max Cable Length
2km
Min Recommended cable size (csa)
1mm
2
Auxiliary relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load
24V, 1A
Fuse (PTC5)
1.1A polyswitch
Max Cable Length
1km
Min Recommended cable size (csa)
2.5mm
2