28
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Technical Specification
It is current limited to 30mA using a resettable polyswitch . Class change and test
conditions do not operate this output . If operated under a fire alarm condition, the
FRE LED will illuminate and will remain illuminated until the fire alarm is reset .
Ensure the polarity of the connections are observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation .
Output to Fire Alarm Protecting Equipment
(Option 7 .10 EN54 Part 2 Option A)
This output, which is fused, and monitored using a 6K8 end of line resistor, is used
for the transmission of the fire signals to controls for automatic fire protecting
equipment (e .g . Door released units etc) . It operates by providing a 24V DC output to
an auxiliary device (e .g . relay) .
It is current limited to 30mA using a resettable polyswitch . Class change and test
conditions do not operate this output . If operated under a fire alarm condition, this
output remains energised until the fire alarm is reset .
Ensure the polarity of the connections is observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation .
Output to Fault Warning Routing Equipment
(Option 8 .9 EN54 Part 2)
This output, which is fused and monitored using a 6K8 end of line resistor, is used
for the transmission of fault signals to fault warning routing equipment . This output
is monitored using a 6K8 end of line resistor and is current limited to 30mA . Under
normal condition it operates by providing 12V DC which can be connected directly to
a 12V auxiliary device (it is current limited to 30mA) .
Under fault conditions or even if the panel is powered down, this output will be
switched to 0V .
Ensure the polarity of the connections is observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation .
Delays to outputs (Option 7.11 EN54 Part 2)
The panel has the option to delay the operation of panel sounders, the Fire Routing
equipment output and the Fire Protecting equipment . This delay is selectable using
the Site Installer download software . The delay is configurable in increments of 1
minute up to a maximum of 10 minutes .
This delay can be enabled and disabled at access level 2 .
The has the facility for a specific call point to override this delay by programming this
call point via an input interface to provide an evacuate signal using the
Site Installer software .