92
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Appendix
Intrinsically Safe Zone Monitor Unit Wiring
To install the device
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface
mounting backbox.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram.
5. Recommended Cable Type: FIRETUF, FP200, MICC
ote:
n
No addressing of the interface is required . See control panel operation for
details . There are no serviceable parts so no maintenance procedures apply .
Figure 59 . standard connections
otes:
n
1. This detection zone can only be used with intrinsically safe detectors
SLR-E-IS (optical)/ DCD-1E-IS (heat) with the non-diode base YBN-R/4IS.
2. The call point zone can only be used with BG3 I/S call points.
3. Only connect cable screen to its adjacent earth terminal.
4. The end of line resistor must always be fitted, each if the spur is unused.
5. Maximum spur length - See BS5839 Pt1:2001 for Zone Coverage.