Technical Specification
Dependencies on more than one alarm signal
Type C (Option 7.12.3 of EN54 Part 2)
The panel has the facility to inhibit the operation of the output sounders, output to
fire alarm routing equipment and the output of the fire alarm protecting equipment
until one more confirmatory signals are received from different zones . This feature is
programmable using the Site Installer software .
Optional Functions as per EN54 Parts 2&4
1. Auxiliary Relay (Option not required by EN54)
This output is a volt free contact, which is protected by a polyswitch . It is rated
at 24V DC 1A . If operated under a fire alarm condition, this output will remain
energised until the fire panel is reset .
DO NOT USE TO SWITCH MAINS VOLTAGE
2. Auxiliary DC Output (Option not defined by EN54)
A 24V DC output is provided . This output is protected by a polyswitch . This output
can be used to power fire or fault auxiliary equipment . Please ensure that all
equipment connected to this output will only draw current when a fire
condition exists .
WArnInG
do noT eXCeed THe rATed ouTPuT CurrenT