33
547 Charger overvoltage
The charger voltage is 10V higher
than the equalizing voltage
Please replace the I/O board
549 Charger undervoltage
Charger voltage is lower than 80% of
battery voltage
Please replace the I/O board
592 Bus-bar short circuit
The bus voltage continuously drops
more than 150V in 3ms
Please replace the power board
594 Bus-bar overvoltage
Bus voltage higher than 450V
Please replace the power board
595 Bus-bar undervoltage
Bus voltage below 286V
Please replace the power board
596 Bus-bar voltage imbalance The difference between the positive
and negative bus voltage is 40V
Please replace the power board
608 Inverter overvoltage
Inverter voltage is 1.05 times higher
than rated
Please replace the power board
609 Inverter undervoltage
Inverter voltage is 0.95 times lower
than rated
Please replace the power board
612 Inverter module 105%
overload
Inverter overload 105 and more than 1
hour
Please remove non-critical loads
613 Inverter module 110%
overload
Inverter overload 110% and more than
1 hour
Please remove non-critical loads
614 Inverter module 125%
overload
Inverter overload 125% and more than
10 minutes
Please remove non-critical loads
615 Inverter module 150%
overload
Inverter overload 150% and more than
1 minute
Please remove non-critical loads
616 Short circuit of inverter
output
Inverter short circuit exceeds 200ms Remove the load and check for a short
circuit
617 Inverter module overload
alarm
Inverter overload 100%
Please remove non-critical loads
626 BYP 125% overload
Bypass overload 125% for more than
10 minutes
Please remove non-critical loads
627 BYP 135% overload
Bypass overload 135% for more than
1 minute
Please remove non-critical loads
628 BYP 150% overload
Bypass overload 150% for more than
1 second
Please remove non-critical loads
629 BYP 200% overload
Bypass overload 200% for more than
20ms
Please remove non-critical loads
630 Bypass overload alarm
Bypass overload 100%
Please remove non-critical loads
640 nverter sofe start fail
The inverter soft start voltage does not
reach 0.9 times the rated voltage
Please replace the power board
642 Frequent switching between
bypass and inverter
Bypass and inverter switching over 5
times within 1 hour
Manually clear faults
644 Parallel operation current
imbalance
The difference between the maximum
and minimum load rates between
parallel UPS systems is more than
30%
Please check whether the parallel
communication is abnormal
Содержание EA990G5
Страница 4: ...7 1 Boards installation 72 7 2 Preparation before power on 72 7 3 Power on and testing 72...
Страница 9: ...5 Fig 2 5 The rear pannel of 30kVA UPS Tower Fig 2 6 The rear pannel of 10kVA 15kVA 20kVA UPS Rack...
Страница 43: ...39 Fig 5 9 The left side board of 15kVA standard model Tower Fig 5 10 The board of 15kVA model Rack...
Страница 48: ...44 Fig 5 19 The left side board of 30kVA standard model Tower...