![East EA990G5 Скачать руководство пользователя страница 75](http://html1.mh-extra.com/html/east/ea990g5/ea990g5_maintenance-manual_3447936075.webp)
71
Table 6-20 The driver test description of 30kVA bypass board
Component and its tag number
Waveform
Remark
Bypass SCR
Q1,Q2,Q3,Q4,Q5,Q6
High level
1V-1.5V
;
Low level
0V
;
If it is found that the individual SCR is abnormally driven during the drive test, please re-check whether the
device is replaced, and check whether the corresponding drive module is damaged.