Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes
unavailable e.g. during a maintenance procedure. (As shown in Fig.3-5).
Fig .3-5 Maintenance mode operation diagram
Danger
During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even
with the LCD turned off.
ECO Mode
To improve system efficiency, UPS rack system works in Bypass mode at normal time, and inverter is
standby. When the utility fails, The UPS transfers to Battery Mode and the inverter powers the loads.
Fig.3-6 ECO Mode operation diagram
Note
There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode, it must be
sure that the interruption has no effect on loads.