Table 2-24 Description of advanced parameters interface
Setting item
Default Options
Description
Working mode
Normal Normal/ECO/Self-ag
e/ Parallel mode
Select the corresponding working mode
according to user needs. It is normal
working mode in general.
Parallel Number 1
1 ~ 4
Set according to the actual frame numbers
of the UPS system installed by the user.
Dev ID
1
1 ~ 16
Set device parallel ID
Output voltage
adjust
0
-5.0 ~ 5.0
Fine tune the output voltage according to
the customer's field power distribution.
Freq track limit ±3Hz
±0.5Hz ~ ±5Hz
Settable, ±0.5Hz ~ ±5Hz, default ±3Hz
Self-age curr
precent (%)
80
30 ~ 100
It is percentage of output current in rated
output current in self-aging mode.
Transformer coil
turns ratio
1
settable
Set the output transformer coil turns ratio.
Byp volt up limt +15%
+10%, +15%, +20%,
+25%
Upper limit: +10%, +15%, +20%, +25%
Byp volt down
limt
-20%
-10%, -15%, -20%,
-30%, -40%
Lower limit: -10%, -15%, -20%, -30%,
-40%
bypass frq range ±5.0
±1.0/±2.0/±3.0/±4.0/±
5.0/±6.0
Note that the bypass frequency range
cannot be less than the ECO frequency
range.
Battery parameters
The interface of battery parameters menu is shown in Fig. 2-27, and the interface description is shown in
Table 2-25.
Fig. 2-27 Battery parameters interface
Table 2-25 Description of battery parameters interface
Содержание EA990G5
Страница 4: ...7 1 Boards installation 72 7 2 Preparation before power on 72 7 3 Power on and testing 72...
Страница 9: ...5 Fig 2 5 The rear pannel of 30kVA UPS Tower Fig 2 6 The rear pannel of 10kVA 15kVA 20kVA UPS Rack...
Страница 43: ...39 Fig 5 9 The left side board of 15kVA standard model Tower Fig 5 10 The board of 15kVA model Rack...
Страница 48: ...44 Fig 5 19 The left side board of 30kVA standard model Tower...