4.2.2.1.1
Parameters
Parameter
Setting
Description
Command on Touch
On / Off / Toggle /
No command
Selects button function when button
touched.
Command on Release On / Off / Toggle /
No command
Selects button function when button
released.
Function of LED
LED permanently Off
LED always Off
LED permanently On
LED always On
Status Indication
Last transmitted command “on” -> LED
on Last transmitted command “off” ->
LED off If “Separate Comm Object”
enabled, status LEDs will wait for
confirmation before changing status.
Inverted Status Indication
Last transmitted command “on” -> LED
off Last transmitted command “off” ->
LED on If “Separate Comm Object”
enabled, status LEDs will wait for
confirmation before changing status.
Operation Indication
Status LED of the touched touch button will
be on for the time period selected at “Light
Duration of LED” parameter at “General”
tab.
Last transmitted command value has no
effect to the status led operation.
Separate Comm Object Enable/
Disable
Only visible when “Function of LED”
selected as “Status Indication” or
“Inverted Status Indication”. This
communication object is the
input of confirmation for status LEDs. If
selected “Enable” respective
communication object should be linked
to an appropriate group address.
Table 16
4.2.2.1.2
Communication Objects
No
Object Name
Function
Data Type
Flags
1
TouchButton1
switch
1 bit
DPT 1.001
CWT
On/Off telegrams will be sent to group address that is linked to this communication object.
3
TouchButton1
Status Comm.Obj. 1 bit
DPT 1.002
CWT
Confirmation for On/Off switch telegrams will be received from this communication object. If these
communications object visible, it must link to an appropriate group address. Otherwise status LEDs will
not function correctly. If status confirmation not to be used the communication object should be
disabled by “Separate Comm Object” parameter.
Table 17