Product Manual Rosa Switch
EAE KNX Rosa Switch
Rosa Switch PB
©
EAE Technology
www.eaetechnology.com
Page
7
/ 26
4.1.1
Parameters
Parameter
Settings
Description
Enable In Operation
Enable/
Disable
In operation can be used to
ensure that device is alive and
connected to KNX line.
In Operation Bit
Off/
On
Visible when “Enable In
Operation” enabled. Bit value
to send as device alive
operation
In Operation Send Interval[sec]
0…
300
…65535
Visible when “Enable In
Operation” enabled. Cyclic time
period for sending in operation
bit
Enable Telegram Limit
Enable
/Disable
Limits the number of telegrams
to send in certain time period
Telegram Limit Period Duration
50ms
, 100ms, …, 30s, 1min
Visible when “Enable
Telegram Limit” enabled.
Time period to check
telegram numbers
Maximum Telegram Count in
Period
1..
100
…255
Visible when “Enable Telegram
Limit” enabled. Maximum
number of telegrams to send in
telegram limit period duration
Light Duration of Status Indication
0,75s
, 2.25s, 3.25s
LEDs on duration when status
LEDs used as operation
indication with rocker or touch
buttons.
Rocker Count
1,
2
, 3, 4, 5, 6
Number of rockers should be
selected compatible with device
to be able to use rockers and
touch buttons correctly.
Duration of Touch Feedback LED
(after release) [0…65535 ms]
0
…
65535
Touch Feedback LEDs lighting
duration after release.
Navigation Light Brightness
[0…100%]
0
…
100%
Navigation LED brightness value
4.1.2
Communication Objects
No
Object Name
Function
Data Type
Flags
0
General – In
operation
Active
1 Bit
DPT 1.002
CT