8.5.2 Switch-on behaviour
This parameter in byte[1] determines the behaviour of the load output of the ESX50D after connection of the
supply voltage.
Value range:
161-163
Default value: 161 (condition before power off)
Data length:
1 byte (unsigned character)
Byte[1 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
condition before power off
(161)
1
0
1
0
0
0
0
1
Off (162)
1
0
1
0
0
0
1
0
On (163)
1
0
1
0
0
0
1
1
fig. 32: Device parameter circuit protector - switch-on behaviour
8.5.3 Overload disconnection
The parameter in byte[2] determines at how many percent of the rated current the ESX50D will signal overload.
Value range:
105 % - 135 % (whole numbers)
Default value:
120 %
Data length:
1 byte (unsigned character)
Byte[2 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 112 %
0
1
1
1
0
0
0
0
fig. 33: Device parameter circuit protector - overload disconnection
8.5.4 Trip time at overload
The parameter in byte[3] determines after which perod in the overload range the load output of the ESX50D
will be disconnected.
Value range:
50 ms – 10,000 ms (whole numbers in 50 ms steps)
Default value: 3000 ms
Data length:
1 byte (unsigned character)
Byte[3 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 3000 ms
50 ms * value (multiplier)
= 50 ms * 60 = 3000 ms
0
0
1
1
1
1
0
0
fig. 34: Device parameter circuit protector - disconnection time overload