8
3.4
Status indication and terminals
Bus Controller
CPC10PB-T1
X81
bus interface
PROFIBUS-DP
Address rotary switch
X61
USB service interface
LED PWR
CPC
10PB
-T1
COM-1
CPC10PB-T4
COM-2
COM-3
COM-4
X51
X52
X53
X54
X61
X81
X51/COM-
1
NS
MS
CM
CE
DC
24 V
X41
PWR
X61
X81
NS
MS
CM
CE
DC
24 V
X41
PWR
Bus Controller
CPC10PB-T4
+ +
0 V 0 V
+ +
0 V 0 V
X41
voltage supply DC 24 V
LED NS
LED MS
LED CM
LED CE
X51, X52,
X53, X54
ELBus®-
connectors
fig. 4: Status indication and terminals CPC10PB-T4
3.4.1 Terminals for voltage supply
The operating voltage of the device is 24 V DC. Faultless operation of the device is ensured in a voltage range
of 18 V to 32 V. Current consumption on duty is typically 60 mA.
Using a supply voltage outside the indicated operating range can cause malfunctions or destruction
of the device.
3.4.2 Connector socket for the
ELBus
®, connector sockets X51, X52, X53, X54
These connector sockets served for connecting the communication unit CPC10 with up to four power distribution
boards SVS201-PWR-xx. Connection of the devices is realised with a one-to-one wiring mode. Preferably it shall
be realised with a cable type H07V-K 1.5mm². The cable does not have to be shielded specially. The cable length
between the bus controller and the power distribution board
SVS201-PWR-xx must not exceed 2 m.
Use of the terminals for applications not provided for in the operation manual or improper connection
can lead to malfunction or destruction of the device.
1. Data line
ELBus® ELB
2. Supply voltage
ELBus® + 24 V
3. Supply voltage
ELBus® GND
fig. 5:
ELBus
® connection
If the terminals of the various power distribution boards SVS201-PWR-xx are swapped, e.g. exchange
X51 with X52, the connected electronic circuit protectors will automatically be parameterised anew.