10
4
Mounting and installation
4.1
Mounting of the system
The preferred mounting position of the
ControlPlex®
system is horizontal.
fig. 6: Installation drawing
4.2
Wiring and connecting the modules
bus controller
CPC10PB-T1
CPC
10PB
-T1
COM-1
CPC10PB-T4
COM-2
COM-3
COM-4
X51
X52
X53
X54
X61
X81
X51/COM-
1
NS
MS
CM
CE
DC
24 V
X41
PWR
X61
X81
NS
MS
CM
CE
DC
24 V
X41
PWR
bus controller
CPC10PB-T4
+ +
0 V 0 V
+ +
0 V 0 V
fig. 7: Terminals CPC10PB-T1 and -T4
4.2.1 Supply of terminal strip X41
Rated voltage:
DC 24 V (18...32 V)
Current ratings:
typically 60 mA
Terminals:
4 x screw terminals, (+/+/0 V/0 V)
Max. cable cross section
max. 2.5 mm
2
Flexible with wire end ferrule without plastic sleeve 0.25 mm – 1.5 mm
2
Flexible with wire end ferrule without plastic sleeve 0.25 mm – 2.5 mm
2
Wire stripping length
7 mm
Tightening torque
0.5 to 0.6 Nm
Содержание ControlPlex CPC10PB