28
8.5.8 Hysteresis of the limit value
This parameter (byte[7]) determines the hysteresis of the limit value current.
Value range:
5 % - 20 % (whole numbers)
Default value: 5 %
Data length:
1 byte (unsigned character)
Byte[7 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 10 %
0
0
0
0
1
0
1
0
fig. 38: Device parameter circuit protector - hysteresis limit value
8.6
Action commands circuit protector
This output byte allows non-cyclical execution of all actions supported by the circuit protector. All actions are
also possible as "broadcast command". This will address all circuit protectors on a PWR board simultaneously. The
index part addressing the slot of the circuit protector has to be set to 99 in this case.
Value range:
112 -118, 126-127
Data length:
1 byte (unsigned character)
Byte[0 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
switch on load output (112)
0
1
1
1
0
0
0
0
switch off load output (113)
0
1
1
1
0
0
0
1
reset load output (114)
0
1
1
1
0
0
1
0
reset error memory (115)
0
1
1
1
0
0
1
1
reset trip counter (116)
0
1
1
1
0
1
0
0
delete bar chart (117)
0
1
1
1
0
1
0
1
reset device parameters
to factory settings (118)
0
1
1
1
0
1
1
0
activate LED
indication (126)
0
1
1
1
1
1
1
0
deactivate LED
indication (127)
0
1
1
1
1
1
1
1
fig. 39: Action commands circuit protector