25
8.4.4 Software version
Byte[7] - Byte[8] contain the software version of the circuit protector The software version is made available
BCD coded. It is coded as follows:
software version = X.Y.Z
High Byte (Bit 12 – Bit 15) = 0
High Byte (Bit 8 – Bit 11) = X
Low Byte (Bit 4 – Bit 7) = Y
Low Byte (Bit 0 – Bit 3) = Z
Value range: 0…65535
Error:
Software version not available (65535)
Data length:
2 byte (unsigned integer)
Byte[7] (LOW) Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
Value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Byte[8] (HIGH) Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
description
32768
16384
8192
4096
2048
1024
512
256
Value
0/1
0
0
0
0/1
0/1
0/1
0/1
fig. 30: Device information circuit protector - software version
8.5
Device parameters circuit protector
8.5.1 Current rating
The parameter in byte[0] determines the current rating of the ESX50D-S100.
Value range:
1 A – 10 A (whole numbers)
Default value: 1 A (only with type ESX50D-S100)
Data length:
1 byte (unsigned character)
Regarding this parameter two types of device have to be distinguished. This parameter is only readable or
writable with type ESX50D-S100. With type ESX50D-S110 this parameter is only readable.
Byte[0 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
Value
1
0
1
0
0/1
0/1
0/1
0/1
1 Ampere (161)
1
0
1
0
0
0
0
1
2 Ampere (162)
1
0
1
0
0
0
1
0
3 Ampere (163)
1
0
1
0
0
0
1
1
4 Ampere (164)
1
0
1
0
0
1
0
0
5 Ampere (165)
1
0
1
0
0
1
0
1
6 Ampere (166)
1
0
1
0
0
1
1
0
7 Ampere (167)
1
0
1
0
0
1
1
1
8 Ampere (168)
1
0
1
0
1
0
0
0
9 Ampere (169)
1
0
1
0
1
0
0
1
10 Ampere (170)
1
0
1
0
1
0
1
0
fig. 31: Device parameters of circuit protector - rating