27
8.5.5 Trip time at short circuit
The parameter in byte[4] determines after which perod in the short circuit range the load output of the ESX50D
will be disconnected.
Value range:
50 ms – 1,000 ms (whole numbers in 10 ms steps)
Default value: 100 ms
Data length:
1 byte (unsigned character)
Byte[4 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 100 ms
10 ms * value (multiplier)
= 10 ms * 10 = 100 ms
0
0
0
0
1
0
1
0
fig. 35: Device parameter circuit protector - disconnection time short circuit
8.5.6 ON delay
The parameter in byte[5] determines the time delay between ON command the switch-on of the load output
of ESX50D
Value range:
50 ms – 2,500 ms (whole numbers in 10 ms steps)
Default value: 100 ms
Data length:
1 byte (unsigned character)
Byte[5 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 50 ms
10 ms * value (multiplier)
= 10 ms * 5 = 50 ms
0
0
0
0
0
1
0
1
fig. 36: Device parameter circuit protector - ON delay
8.5.7 Limit value load current
The parameter in byte[6] determines at how many percent of the rated current the ESX50D will signal "limit
value exceeded".
Value range:
50 % - 100 % (whole numbers)
Default value: 80 %
Data length:
1 byte (unsigned character)
Byte[6 ]
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Example: 100 %
0
1
1
0
0
1
0
0
fig. 37: Device parameter circuit protector - limit value load current